440.9 Grounding and Bonding.

Even though EMT is recognized as an equipment grounding conductor in 250.118, if installed outdoors on a rooftop to serve HVAC equipment, it requires a wire type equipment grounding conductor in the raceway.
Click to Enlarge

Even though EMT is recognized as an equipment grounding conductor in 250.118, if installed outdoors on a rooftop to serve HVAC equipment, it requires a wire type equipment grounding conductor in the raceway.

Since 2017, the NEC® has required a wire type equipment grounding conductor for outdoor metal raceways supplying rooftop HVAC equipment supplied by metal raceways made up with compression-type fittings.

The idea is to avoid a common occurrence where a non-threaded raceway such as EMT is installed (serving as the wiring method and the equipment grounding conductor) and the fittings eventually come loose, compromising the effective ground-fault current return path. Having a wire type equipment grounding conductor inside the metal raceway helps to ensure that the effective ground-fault current path is maintained even if the raceway fittings loosen up over time.

The code language exempts Intermediate Metal Conduit (IMC) or Rigid Metal Conduit (RMC) from requiring a wire type equipment grounding conductor since both IMC and RMC are threaded metal raceways and less likely to come apart when jarred or tripped on, however, any IMC or RMC that has been cut and is coupled or connected with a compression fitting would be required to contain the wire type equipment grounding conductor.

Below is a preview of the NEC®. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to NFPA 70.

2026 Code Language:

440.9 Grounding and Bonding. Where equipment is installed outdoors on a roof, an equipment grounding conductor of the wire type shall be installed in outdoor portions of metallic raceway systems that use compression-type fittings.

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

440.9 Grounding and Bonding.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Which of the following is true for outdoor rooftop mounted HVAC equipment?

A: A metal raceway using compression-type fittings can serve as the equipment grounding conductor.
B: An outdoor RMC raceway using only threaded fittings can NOT serve as the equipment grounding conductor.
C: A plastic raceway using glued fittings can serve as the equipment grounding conductor.
D: A wire type equipment grounding conductor shall be installed in outdoor portions of metallic raceway systems that use compression-type fittings.
Please register or sign in for electrical continuing education courses.

If you were already signed in, your session probably expired, please sign back in.