These are utility grade DC solar heat generators that direct sunlight into a Stirling engine.
Section 250.166 provides rules on proper sizing of a DC grounding electrode conductor (GEC).
DC grounding electrodes and grounding electrode conductors are sometimes required for specific DC systems such as solar photovoltaic systems and fuel cells.
The code language in the parent text of 250.166 makes it clear that the DC GEC is never required to be larger than 3/0 copper or 250 kcmil aluminum even if the conductors supplied by the DC system exceed those values.
Below is a preview of the NEC®. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to NFPA 70.
2026 Code Language:
250.166 Size of the Direct-Current Grounding Electrode Conductor. The size of the grounding electrode conductor for a dc system shall be as specified in 250.166(A) and 250.166(B), except as permitted by 250.166(C) through 250.166(E). The grounding electrode conductor for a dc system shall meet the sizing requirements in this section but shall not be required to be larger than 3/0 copper or 250 kcmil aluminum or copper-clad aluminum.
Which of the following is true of a DC grounding electrode conductor terminating from an underground metal water pipe to an enclosure where the DC system supplies 350 kcmil copper circuit conductors?