An equipment grounding conductor passing through the box without a splice is not required to be joined inside the box to others that are spliced in the box.
Section 250.148 addresses the continuity of equipment grounding conductors and their attachment in boxes.
Not all boxes are metal or provide continuity. Some boxes are plastic and have no provisions to attach an equipment grounding conductor to the box. In a plastic box, continuity is maintained between the equipment grounding conductors by joining them together inside the box rather than connecting them “to” the box.
In a metal box, a wire type equipment grounding conductor can be attached to the box with a ground screw or clip and terminated to the switch or receptacle in the box. If metal raceways such as EMT are connected to a metal box, then in most cases, a wire type equipment grounding conductor is not required inside the raceways since EMT is recognized as an equipment grounding conductor according to 250.118(4).
Section 250.148 provides all of the methods permitted for ensuring proper continuity between the equipment grounding conductors when a box is installed, and circuit conductors are spliced within the box or terminated on equipment within or supported by the box.
Below is a preview of the NEC®. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to NFPA 70.
2026 Code Language:
250.148 Continuity of Equipment Grounding Conductors and Attachment in Boxes. If circuit conductors are spliced within a box or terminated on equipment within or supported by a box, the installation shall comply with 250.148(A) through 250.148(D).
(A) Connections and Splices. All equipment grounding conductors that are spliced or terminated within the box shall be connected together. Connections and splices shall be made in accordance with 110.14(B) and 250.8 except that insulation shall not be required.
(B) Equipment Grounding Conductor Continuity. The arrangement of grounding connections shall be such that the disconnection or the removal of a luminaire, receptacle, or other device fed from the box does not interrupt the electrical continuity of the equipment grounding conductor(s) providing an effective ground-fault current path.
(C) Metal Boxes. A connection used for no other purpose shall be made between the metal box and the equipment grounding conductor(s). The equipment bonding jumper or equipment grounding conductor shall be sized from Table 250.122 based on the largest OCPD protecting circuit conductors in the box.
(D) Nonmetallic Boxes. One or more equipment grounding conductors brought into a nonmetallic outlet box shall be arranged to provide a connection to any fitting or device in that box requiring connection to an equipment grounding conductor.
Based on the 2026 NEC, which of the following is true?