All equipment grounding conductors in the gutter must be joined together.
Several rules must be followed when installing conductors in parallel. Most of the rules for parallel conductors are found in 310.10(G) and additional rules pertaining to installing equipment grounding conductors in parallel are located in 250.122(H).
The rules for parallel equipment grounding conductors in multiconductor cables are kept separate from individual parallel equipment grounding conductor installations in raceways or cable trays.
If a sheet metal auxiliary gutter is installed and supplied by multiconductor cables in parallel, the gutter is required to be connected to the equipment grounding conductors in each parallel cable. These equipment grounding conductors must be sized from Table 250.122 based on the size of the overcurrent device protecting the multiconductor cables.
Section 250.122(H)(2)(c) allows a single equipment grounding conductor, sized in accordance with 250.122, in combination with the equipment grounding conductors provided within the multiconductor cables. This allowance recognizes that situations can occur where the equipment grounding conductor in each parallel multiconductor cable may not be sufficient in size for larger feeders or branch circuits in the same auxiliary gutter. In this case, an individual equipment grounding conductor is permitted to be installed in addition to the equipment grounding conductors provided within the multiconductor cables as long as all equipment grounding conductors are connected together.
Below is a preview of the NEC®. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to NFPA 70.
2026 Code Language:
250.122(H) Conductors in Parallel. For circuits of parallel conductors as permitted in 310.10(H), the equipment grounding conductor shall be installed in accordance with (1) or (2).
(1) Conductor Installations in Raceways, Auxiliary Gutters, or Cable Trays.
(a) Single Raceway or Cable Tray, Auxiliary Gutter, or Cable Tray. If circuit conductors are connected in parallel in the same raceway, auxiliary gutter, or cable tray, a single wire-type conductor sized in accordance with 250.122 based on the OCPD for the feeder or branch circuit shall be permitted as the EGC.
(b) Multiple Raceways. If conductors are installed in multiple raceways and are connected in parallel, a wire-type EGC, if used, shall be installed in each raceway, be connected in parallel, and comply with the following:
(1) The EGC installed in each raceway shall be sized in accordance with 250.122 based on the rating of the OCPD for the feeder or branch circuit.
(2) The EGC in each raceway shall not be required to be larger than the largest ungrounded conductor in the raceway.
(c) Wire-Type Equipment Grounding Conductors in Cable Trays. Wire-type EGCs installed in cable trays shall meet the minimum requirements of 392.10(B)(1)(c).
(d) Metal Raceways, Auxiliary Gutters, or Cable Trays. Metal raceways or auxiliary gutters in accordance with 250.118(A) or cable trays complying with 392.60(B) shall be permitted as EGCs.
(2) Multiconductor Cables.
(a) Except as provided in 250.122(H)(2)(c) for raceway, trench, or cable tray installations, the EGC in each multiconductor cable shall be sized in accordance with 250.122 based on the OCPD for the feeder or branch circuit.
(b) If circuit conductors of multiconductor cables are connected in parallel, the EGC(s) in each cable shall be connected in parallel.
(c) If multiconductor cables are paralleled in the same raceway, auxiliary gutter, trench, or cable tray, a single EGC that is sized in accordance with 250.122 shall be permitted in combination with the EGCs provided within the multiconductor cables and shall all be connected together.
(d) EGCs installed in cable trays shall meet the minimum requirements of 392.10(B)(1)(c). Cable trays complying with 392.60(B), metal raceways complying with 250.118(A), or auxiliary gutters shall be permitted as EGCs.
Based on 250.122(H)(2)(a), which of the following is true when installing multiconductor cables in parallel to supply a sheet metal auxiliary gutter?