250.80 Service Raceways and Enclosures.

Similar code language is located in 250.86 for other than service raceways.
Click to Enlarge

Similar code language is located in 250.86 for other than service raceways.

One main rule for grounded electrical systems is that all metal enclosures and raceways for service conductors and equipment must be connected to the grounded system conductor.

This rule applies to all metal enclosures and raceways containing service conductors, including metal pull elbows that are installed in a run of underground nonmetallic service raceway.

The exception allows an isolated metal component to remain ungrounded if it has a minimum cover of 18 in. to all parts of the metal component.

Similar language can be found in 250.86 pertaining to isolated metal components used in underground runs of nonmetallic raceways, other than service raceways.

Below is a preview of the NEC®. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to NFPA 70.

2026 Code Language:

250.80 Service Raceways and Enclosures. Metal enclosures and raceways for service conductors and equipment shall be connected to the grounded conductor if the electrical system is grounded or to the grounding electrode conductor for electrical systems that are not grounded.

Exception: Metal components that are installed in a run of underground nonmetallic raceway(s) and are isolated from possible contact by a minimum cover of 18 inches to all parts of the metal components shall not be required to be connected to the grounded conductor, supply-side bonding jumper, or grounding electrode conductor.

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

250.80 Service Raceways and Enclosures.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Which of the following metal components in a run of underground nonmetallic service raceway can remain ungrounded?

A: An isolated metal pull elbow installed so that all parts of the elbow have at least 18 inches of cover.
B: An isolated metal pull elbow installed so that the elbow has 12 inches of cover.
C: A metal pull elbow installed so that the elbow emerges from grade.
D: A rigid metal pull elbow installed so that the elbow has 6 inches of cover.
Please register or sign in for electrical continuing education courses.

If you were already signed in, your session probably expired, please sign back in.