250.70 Methods of Grounding and Bonding Conductor Connection to Electrodes.

The grounding or bonding conductor shall be connected to the grounding electrode by exothermic welding, listed lugs, listed pressure connectors, listed clamps, or other listed means.
Click to Enlarge

The grounding or bonding conductor shall be connected to the grounding electrode by exothermic welding, listed lugs, listed pressure connectors, listed clamps, or other listed means.

There are many ways to properly make a grounding or bonding connection. Section 250.8 provides a number of allowable items suitable to be used for grounding and bonding connections, most of which require “listing”, also called product certification.

A product that is “listed” (certified) had been tested to the appropriate product safety standard (such as UL 467 for Grounding and Bonding Equipment) and found to be acceptable and suitable for the intended purpose.

“Listed” is defined in Article 100 as:

Listed. Equipment, materials, or services included in a list published by an organization that is acceptable to the authority having jurisdiction and concerned with evaluation of products or services, that maintains periodic inspection of production of listed equipment or materials or periodic evaluation of services, and whose listing states that either the equipment, material, or service meets appropriate designated standards or has been tested and found suitable for a specified purpose.

Informational Note: The means for identifying listed equipment may vary for each organization concerned with product evaluation, some of which do not recognize equipment as listed unless it is also labeled. Use of the system employed by the listing organization allows the authority having jurisdiction to identify a listed product.

Section 250.70 is specific to the actual connection of the grounding electrode conductor to a grounding electrode described in 250.52 and provides a list similar to Section 250.8(A).

According to 250.70, the grounding or bonding conductor shall be connected to the grounding electrode by exothermic welding, listed lugs, listed pressure connectors, listed clamps, or other listed means.

Below is a preview of the NEC®. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to NFPA 70.

2026 Code Language:

250.70 Methods of Grounding and Bonding Conductor Connection to Electrodes.

(A) General. Ground clamps shall be listed for both grounding electrode and grounding electrode conductor materials. Only one conductor shall be permitted to be connected to the grounding electrode by a single clamp or fitting unless the clamp or fitting is listed for multiple conductors.

(1) Connections. Grounding or bonding conductors shall be connected to grounding electrodes by any of the following means:

(1) Exothermic welding

(2) Listed lugs

(3) Listed pressure connectors

(4) Listed clamps

(5) Other listed means

(2) Ground Clamps for Direct Burial or Concrete Encasement. Ground clamps used on pipes, rods, or other buried electrodes shall be listed for direct soil burial or concrete encasement.

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

250.70 Methods of Grounding and Bonding Conductor Connection to Electrodes.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Which of the following is true regarding the connection of a grounding electrode conductor to the grounding electrode?

A: Only one conductor shall be permitted to be connected to the grounding electrode by a single clamp or fitting unless the clamp or fitting is listed for multiple conductors.
B: The only permitted method is exothermic welding.
C: The only permitted method is a ground clamp.
D: The only permitted method is a terminal bar.
Please register or sign in for electrical continuing education courses.

If you were already signed in, your session probably expired, please sign back in.