250.64(E) Raceways, Cable Armor, and Enclosures for Grounding Electrode Conductors.

Cable armor is similar to armored cable type AC, but there is little space between the armor and the conductor inside.
Click to Enlarge

Cable armor is similar to armored cable type AC, but there is little space between the armor and the conductor inside.

NEC Section 210.64(E) provides requirements for ferrous metal raceways, cable armor, and enclosures that contain a grounding electrode conductor. Ferrous metals contain appreciable amounts of iron such as steel and are usually magnetic. A non-ferrous metal does not have magnetic properties and includes metals such as aluminum and copper.

The general rule for ferrous metal raceways and enclosures containing a grounding electrode conductor requires them to be electrically continuous from the point of attachment to cabinets or equipment to the grounding electrode and to be securely fastened to the ground clamp or fitting.

Cable armor must also comply with this section. Cable armor is similar to armored cable type AC, but there is little space between the armor and the conductor inside. The NEC® does not have a specific article covering cable armor. Most cable armor is made of a ferrous galvanized steel interlocking armor applied over a bare conductor (see image).

The code language requires ferrous metal raceways, enclosures, and cable armor to be bonded at each end of the raceway or enclosure to the grounding electrode or grounding electrode conductor to create an electrically parallel path. Bonding methods permitted to accomplish this include the following three methods from Section 250.92(B)(2) through (4):

·       Connections made up wrenchtight using threaded couplings, threaded entries, or listed threaded hubs on enclosures

·       Threadless couplings and connectors if made up tight for metal raceways and metal-clad cables

·       Other listed devices, such as bonding-type locknuts, bushings, or bushings with bonding jumpers

There are listed fittings that are suitable to bond cable armor to the service enclosure, but many electricians select the wrong product to use on the other end when bonding cable armor to the actual grounding electrode within.

Below is a preview of the NEC®. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to NFPA 70.

2026 Code Language:

250.64(E) Raceways, Cable Armor, and Enclosures for Grounding Electrode Conductors.

(1) General. Raceways, cable armor, and enclosures that contain grounding electrode conductors shall comply with 250.64(E)(1)(a) or 250.64(E)(1)(b).

(a) Ferrous metal raceways, enclosures, and cable armor for grounding electrode conductors shall comply with the following:

(1) Be electrically continuous from the point of attachment to cabinets or equipment to the grounding electrodes.

(2) Be securely fastened to ground clamps or fittings.

(3) Be bonded at each end of the raceway, cable armor, or enclosure to the grounding electrode or grounding electrode conductor to create an electrically parallel path.

(b) Nonferrous metal raceways, enclosures, and cable armor shall not be required to be electrically continuous.

(2) Methods. Bonding shall be in compliance with 250.92(B) and ensured by one of the methods in 250.92(B)(2) through 250.92(B)(4).

(3) Size. The bonding jumper for a grounding electrode conductor(s), raceway(s), enclosure(s), or cable armor shall be the same size as, or larger than, the largest enclosed grounding electrode conductor.

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

250.64(E) Raceways, Cable Armor, and Enclosures for Grounding Electrode Conductors.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Based on the 2026 NEC, which of the following is true?

A: The rules in 250.64(E) apply to non-ferrous cable armor.
B: The rules in 250.64(E) apply to ferrous cable armor.
C: Bonding each end of cable armor containing a grounding electrode conductor is not required.
D: Ferrous metal raceways, enclosures, and cable armor shall not be required to be electrically continuous.
Please register or sign in for electrical continuing education courses.

If you were already signed in, your session probably expired, please sign back in.