250.64(D)(1)(b)(3) Building or Structure with Multiple Disconnecting Means in Separate Enclosures. Common Grounding Electrode Conductor and Taps.

Common hot gutter type service installation with the grounding electrode conductors connected to the exposed copper grounding busbar.
Click to Enlarge

Common hot gutter type service installation with the grounding electrode conductors connected to the exposed copper grounding busbar.

Not all disconnects for a building are required to be in the same distribution panel or enclosure. Many buildings have one common hot gutter that supplies several individual separate disconnect enclosures, grouped in one location.

For this type of installation, one grounding electrode system can be installed and shared by all of the separate service disconnect switches. One way to accomplish this is to use a single grounding electrode conductor, run from the grounding electrode system up to a common busbar of a certain dimension, and then individual GEC taps can be made from the busbar to each individual disconnecting means enclosure.

Section 250.64(D)(1)(b)(3) requires the GEC busbar to be at least ¼ in. thick X 2 in. wide and of sufficient length to accommodate the number of terminations needed for the installation.

Below is a preview of the NEC®. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to NFPA 70.

2026 Code Language:

250.64(D)(1) Common Grounding Electrode Conductor and Taps.

(b)(3) Connections to an aluminum or copper busbar as follows:

a. Busbars shall be not less than 1⁄4 in. thick × 2 in. wide and of a length to accommodate the number of terminations necessary for the installation.

b. Busbars shall be securely fastened and installed in an accessible location.

c. Connections shall be made by listed connectors or by the exothermic welding process.

d. If aluminum busbars are used, installation shall comply with 250.64(A).

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

250.64(D)(1)(b)(3) Building or Structure with Multiple Disconnecting Means in Separate Enclosures. Common Grounding Electrode Conductor and Taps.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Which of the following is required for a busbar used for GEC taps to a common grounding electrode conductor?

A: Connections to it can only be made by mechanical devices.
B: Connections to it can only be made by the exothermic welding process.
C: The busbar shall be installed in a readily accessible location.
D: The busbar shall be securely fastened and shall be installed in an accessible location.