250.28(A) Main Bonding Jumper and System Bonding Jumper Material.

NEC 250.28(A) permits aluminum and copper-clad aluminum main bonding jumpers which aligns with Table 250.102(C)(1).
Click to Enlarge
NEC 250.28(A) permits aluminum and copper-clad aluminum main bonding jumpers which aligns with Table 250.102(C)(1).

Main bonding jumpers are permitted to be made of aluminum and copper-clad aluminum. Table 250.102(C)(1) specifies the minimum size main bonding jumper permitted based on the conductor material type.

Section 250.28(A) provides a list of items and conductors suitable to be used as a main bonding jumper which aligns with materials shown in Table 250.102(C)(1).

Below is a preview of the NEC®. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to NFPA 70.

2026 Code Language:

250.28(A) Material. Main bonding jumpers and system bonding jumpers shall be of copper, aluminum, copper-clad aluminum, or other corrosion-resistant material. A main bonding jumper and a system bonding jumper shall be a wire, bus, screw, or similar suitable conductor.

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

250.28(A) Main Bonding Jumper and System Bonding Jumper Material.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Refer to the image of NEC Table 250.102(C)(1):

What is the minimum size aluminum main bonding jumper permitted if the ungrounded conductors are 500 kcmil aluminum?

A: 1/0 AWG aluminum.
B: 2/0 AWG aluminum.
C: 3/0 AWG aluminum.
D: 4/0 AWG aluminum.