Equipment Grounding Conductors.

Many raceway types qualify as an equipment grounding conductor.
Click to Enlarge

Many raceway types qualify as an equipment grounding conductor.

Grounding is the process of connecting something to the earth. An equipment grounding conductor (EGC) connects the non-current carrying metal parts of equipment and metal enclosures to the grounded conductor at the service (which is connected to earth) and provides a low impedance path (an Effective Ground-Fault Current Path) to carry fault current in the event of a fault to ground occurring in an electrical system circuit.

An effective ground-fault current path ensures that the ground-fault current is returned to the source (usually the utility transformer or customer owned transformer) which causes the overcurrent device (fuse or circuit breaker) to open (trip).

NEC Section 250.118 provides a list of items that can be used as an equipment grounding conductor including:

(1) A copper, aluminum, or copper-clad aluminum conductor. This conductor shall be solid or stranded; insulated, covered, or bare; and in the form of a wire or a busbar of any shape.

(2) Rigid metal conduit.

(3) Intermediate metal conduit.

(4) Electrical metallic tubing.

(5) Listed flexible metal conduit meeting specific conditions.

(6) Listed liquidtight flexible metal conduit meeting specific conditions.

(7) Flexible metallic tubing where the tubing is terminated in listed fittings and meets specific conditions.

(8) Armor of Type AC cable as provided in 320.108.

(9) The copper sheath of mineral-insulated, metal-sheathed cable Type MI.

(10) Type MC cable under certain conditions.

(11) Cable trays as permitted in 392.10 and 392.60.

(12) Cablebus framework as permitted in 370.60(1).

(13) Other listed electrically continuous metal raceways and listed auxiliary gutters.

(14) Surface metal raceways listed for grounding.

Below are a few of the NEC® Article 100 definitions pertaining to grounding:

Below is a preview of the NEC®. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to NFPA 70.

2026 Code Language:

Article 100:

Effective Ground-Fault Current Path. An intentionally constructed, low-impedance electrically conductive path designed and intended to carry current during ground-fault events from the point of a ground fault on a wiring system to the electrical supply source and that facilitates the operation of the overcurrent protective device (OCPD) or ground-fault detectors.

Ground. The earth.

Grounded (Grounding). Connected (connecting) to ground or to a conductive body that extends the ground connection.

Ground-Fault Current Path. An electrically conductive path from the point of a ground fault on a wiring system through normally non–current-carrying conductors, grounded conductors, equipment, or the earth to the electrical supply source.

Informational Note: Examples of ground-fault current paths are any combination of equipment grounding conductors, metallic raceways, metallic cable sheaths, electrical equipment, and any other electrically conductive material such as metal, water, and gas piping; steel framing members; stucco mesh; metal ducting; reinforcing steel; shields of communications cables; grounded conductors; and the earth itself.

Grounding Conductor, Equipment (EGC). A conductive path(s) that is part of an effective ground-fault current path and connects normally non–current-carrying metal parts of equipment together and to the system grounded conductor or to the grounding electrode conductor, or both.

Informational Note No. 1: It is recognized that the equipment grounding conductor also performs bonding.

Informational Note No. 2: See 250.118 for a list of acceptable equipment grounding conductors.

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

Equipment Grounding Conductors.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Which of the following can be used as an equipment grounding conductor?

A: Electrical metallic tubing.
B: Electrical Nonmetallic Tubing.
C: PVC conduit.
D: Flexible cord.
Please register or sign in for electrical continuing education courses.

If you were already signed in, your session probably expired, please sign back in.