Now that the calculation has been performed, the inspector can verify that the correct conductor size, length and type has been installed in order to get the available fault current down to 5,000 amps to match the SCCR on the control panel.
Most multimotor and combination-load equipment is already required by Section 440.4(B) to be marked with a short-circuit current rating (SCCR). The intent is so that the electrician and inspector can ensure compliance with NEC® 110.9 and 110.10.
The only way to ensure the HVAC equipment is rated to handle the amount of short circuit current available is to first find out the maximum amount of Available Fault Current that could be delivered to the equipment during a short circuit condition and then to determine the SCCR of the equipment by looking at the nameplate. As long as the HVAC equipment has a SCCR equal to or greater than the available short circuit current, then the installation complies with NEC® 110.10.
NEC Section 440.10(A) requires motor controllers of multimotor and combination-load equipment to be installed in a location where the available fault current does not exceed the SCCR of the equipment. As well, subsection B states: “When motor controllers or industrial control panels of multimotor and combination-load equipment are required to be marked with a short circuit current rating, the available fault current and the date the available fault current calculation was performed shall be documented and made available to those authorized to inspect, install, or maintain the installation”.
Knowing the amount of available short circuit current at the HVAC equipment is the first step in ensuring that the HVAC equipment is properly rated for the worst-case fault condition that it may see.
See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on the “free access” tab and select the applicable year of NFPA 70 (National Electrical code).
2020-2026 Code Language:
440.10 Short-Circuit Current Rating.
(A) Installation. Motor controllers or industrial control panels of multimotor and combination-load equipment shall not be installed where the available fault current exceeds its short-circuit current rating as marked in accordance with 440.4(B).
(B) Documentation. When motor controllers or industrial control panels of multimotor and combination-load equipment are required to be marked with a short circuit current rating, the available fault current and the date the available fault current calculation was performed shall be documented and made available to those authorized to inspect, install, or maintain the installation.
Which of the following is true for HVAC multimotor and combination load equipment with a marked short-circuit current rating?
| Please register or sign in for electrical continuing education courses. If you were already signed in, your session probably expired, please sign back in. |