Quite often, equipment will only have a short-circuit current rating (SCCR) when protected by a specific type of overcurrent protective device (OCPD). Using any other type of OCPD other than what is marked on the equipment will not be guaranteed to achieve the desired SCCR.
Sometimes the equipment will have a label that has blanks to be filled in by the site electrician based on the field conditions and the amount of Available Fault Current (AFC). Quite often a specific fuse will be chosen based on its current limiting characteristics and using the up-over-down method on the fuse chart.
An experienced electrician will know more than just how to hang conduit and pull wire. Basic electrical theory, impedance, resistance and overcurrent device characteristics must be understood in order to make an installation compliant with NEC® 110.9 and 110.10.
See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on the “free access” tab and select the applicable year of NFPA 70 (National Electrical code).
2017-2023 Code Language:
110.10 Circuit Impedance, Short-Circuit Current Ratings, and Other Characteristics. The overcurrent protective devices, the total impedance, the equipment short-circuit current ratings, and other characteristics of the circuit to be protected shall be selected and coordinated to permit the circuit protective devices used to clear a fault to do so without extensive damage to the electrical equipment of the circuit…
2026 Code Language:
110.10 Available Fault Current, Short-Circuit Current Ratings, and Other Characteristics. The OCPDs, equipment short-circuit current ratings, and other characteristics of the circuit to be protected shall be selected and coordinated with the available fault current to permit the circuit protective devices used to clear a fault to do so without extensive damage to the electrical equipment of the circuit. Listed equipment applied in accordance with their listing shall be considered to meet the requirements of this section.
Refer to the image.
If a class T fuse is not used and the AFC is 65kA, what else can be used ahead of the chiller to ensure that the SCCR of the chiller control panel is properly protected?
| Please register or sign in for electrical continuing education courses. If you were already signed in, your session probably expired, please sign back in. |