The Ugly’s Electrical References guide has many tables and formulas commonly used by the electrician.
Available Fault Current (AFC) calculations are most often performed by using fault current calculating software or spreadsheets that automatically calculate the final amount of AFC after entering specific values. Long before this type of software became available, the calculation was done manually with a few basic formulas that are commonly found in many of the electrician’s pocket guides like the “Ugly’s Electrical References” guide. These types of guides provide the most common electrical references and formulas used by the electrician. It is important to understand how the basic formula works even if the plan is to use software for the calculation.
Take special note of the image from the Ugly’s guide where the side in red represents the C value for conductors in a raceway, and the side in blue is based on conductors in a cable type wiring method.
Some formulas will calculate the AFC on the secondary side of the transformer and other formulas will calculate the AFC at the end of a run of conductor. Below is a 3-step formula to calculate three-phase AFC, also called the available short circuit current (ISC) at the end of a run of wire. In order to use the calculation, several factors must be known:
Step 1:
F = (1.732 X L X I) ÷ (C X E_(L_L))
Step 2:
Multiplier (M) = 1 ÷ (1 + F)
Step 3:
Available Short-Circuit Current (ISC) = I X M
Refer to the image.
What is the C value for an installation where 3 single 4/0 AWG copper conductors operating at 600 volts or less are installed in a PVC (nonmagnetic) conduit?
| Please register or sign in for electrical continuing education courses. If you were already signed in, your session probably expired, please sign back in. |