Available Fault Current and Characteristics of the Circuit.

Typical letter from the utility company providing the AFC at a given point.
Click to Enlarge

Typical letter from the utility company providing the AFC at a given point.

The final amount of Available Fault Current (AFC) at a given point depends on several factors and can change by modifying any one of them. The following items are all characteristics of the circuit that need to be considered when selecting equipment ratings according to NEC® 110.10:

·       Length of wire. A longer run of wire results in less available fault current at the end of the run of wire than the same type and size of wire installed in a shorter length. This is due to the difference in resistance.

·       Size of wire. Larger conductors have less resistance, allowing more fault current to flow. Smaller conductors increase resistance and reduce the available fault current at the end of the run.

·       Type of wire. Copper is a better conductor of electricity than aluminum which means using a copper wire where aluminum was specified, results in a higher amount of AFC at the end of the run of wire.

·       Raceway or cable. Conductors in a cable will have a different AFC value at the end of the cable run than the same type, length and size wires installed in a raceway.

·       Type of raceway. Installing conductors in a ferrous metal raceway will result in a lower amount of AFC than the same size, type and length of conductors installed in a plastic raceway because of the current that will be lost through induction on the metal raceway which does not occur with a plastic conduit.

When the electrical utility company provides an AFC value at the service equipment, it will be based on the type, size and length of service entrance conductors installed from the secondary spades of the utility transformer to the service equipment. As well, they will consider the number of parallel runs and if the conductors are installed in a plastic or ferrous metal raceway.

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

Available Fault Current and Characteristics of the Circuit.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Which of the following is true of Available Fault Current?

A: Type of raceway has no impact on the final amount of AFC at the end of a run of wire.
B: Type of wire has no impact on the final amount of AFC at the end of a run of wire.
C: Moving a service panel further away from the utility transformer than originally shown on the plans will result in a higher amount of available fault current at the service panel.
D: Moving a service panel closer to the utility transformer than originally shown on the plans can result in a higher amount of available fault current at the service panel.