314.2 Listing.

Outlet boxes used to provide mechanical support for ceiling fans shall be listed for fan support.
Click to Enlarge

Outlet boxes used to provide mechanical support for ceiling fans shall be listed for fan support.

Code Change Summary: New Section 314.2 provides listing requirements for equipment covered by Article 314.

SME commentary: In the 2026 NEC®, a new Section 314.2 was added to identify all equipment within Article 314 that requires product certification (Listing). The words “listed” and “listing” continue to appear throughout the article, but most prior references were associated with installation or application requirements rather than explicitly identifying which products must be listed. This new section consolidates and clarifies those requirements, improving usability and consistency with the NEC® Style Manual.

Section 314.2 organizes the listing requirements into eight specific product categories, each representing types of equipment that must be listed when installed in accordance with Article 314. Under the new code language, the following shall be listed:

By placing these requirements in one location, users can now easily determine which equipment governed by Article 314 must be listed products.

Before the 2026 revision, the article contained more than thirty individual references to listed products scattered throughout various subsections. The NEC® Style Manual instructs each article to consolidate such requirements into its .2 section, ensuring clear and centralized identification of all products requiring listing. The Code-Making Panel (CMP-8) reviewed every reference to determine which items fell within the purview of Article 314 and which were better addressed in other articles or under the authority of other code-making panels.

Below is a preview of the NEC®. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to the 2026 NEC® edition of NFPA 70.

2023 Code Language:

This code language did not exist.

2026 Code Language:

314.2 Listing Requirements. The equipment specified in 314.2(A) through 314.2(H) shall be listed.

(A) Extenders. Extenders for device boxes shall be listed.

(B) Drain Fittings. Drain fittings larger than 6 mm (1⁄4 in.) shall be listed.

(C) Floor Boxes.

(1) General. Floor boxes and floor box covers shall be listed.

(2) Show Windows. Where located in the floor of show windows or other display applications and determined by the authority having jurisdiction to be free from likely exposure to physical damage, moisture, or dirt, boxes shall be permitted to be other than those listed for floor applications. Receptacles and covers shall be listed as an assembly for such applications.

(D) Boxes at Ceiling-Suspended (Paddle) Fan Outlets. Outlet boxes used to provide mechanical support for ceiling-suspended (paddle) fans shall be listed for fan support as required in 314.27(B)…

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

314.2 Listing.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Based on NEC 314.2, which of the following shall be listed?

A: All boxes.
B: Vertical surface outlets.
C: Box extenders.
D: Partitions.
Please register or sign in for electrical continuing education courses.