210.8(A)(10) Ground-Fault Circuit-Interrupter Protection for Personnel. Laundry Areas.

GFCI protection is required for the receptacle circled in red. The GFCI device must be readily acessible which means that it cannot be installed behind the heavy washing machine.
Click to Enlarge
GFCI protection is required for the receptacle circled in red. The GFCI device must be readily acessible which means that it cannot be installed behind the heavy washing machine.

Code Change Summary: A new subsection was added to require ground-fault circuit-interrupter protection (GFCI protection), for 125-volt, single-phase, 15- and 20-ampere receptacles installed in dwelling unit laundry areas.

In the previous 2011 NEC®, GFCI protection was required for 125-volt, single-phase, 15- and 20-ampere receptacles installed within 6 ft. of any dwelling unit sink, which included laundry room wash tubs or sinks. If a sink or wash tub was not present in the laundry room, then no GFCI protection was required for laundry room receptacles.

Now GFCI protection is required for any 125-volt, single-phase, 15- or 20-ampere receptacle installed within the laundry area, even if no sink is present.

It’s important to remember that all GFCI type devices (GFCI type circuit breakers or receptacles) must also be readily accessible. This means that if using a GFCI type receptacle for the laundry room washing machine, it cannot be located directly behind the washing machine. The best idea is to locate the receptacle behind the washer but above it so that the homeowner can access the test and reset buttons for monthly testing.

Below is a preview of the NEC®.  See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on the “free access” tab and select the applicable year of NFPA 70 (National Electrical code).

2014 Code Language:

210.8(A) Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in 210.8(A)(1) through (10) shall have ground-fault circuit-interrupter protection for personnel.

(10) Laundry areas.

Did You Like This? Let Us Know With A Like! Thanks!

210.8(A)(10) Ground-Fault Circuit-Interrupter Protection for Personnel. Laundry Areas.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Which of the following is true of a 125-volt, single-phase, 20-ampere dwelling unit receptacle installed in the laundry room?

A: It does NOT require GFCI protection.
B: It is NOT required to be accessible.
C: It requires GFCI protection even if the closest sink is 10 feet away.
D: It only requires GFCI protection if there is a sink in the room.
Please register or sign in for electrical continuing education courses.

If you were already signed in, your session probably expired, please sign back in.