250.104(B) Bonding of Piping Systems and Exposed Structural Metal. Other Metal Piping.

NEC 250.8 requires a listed clamp when bonding the gas piping system.
Click to Enlarge
NEC 250.8 requires a listed clamp when bonding the gas piping system.

Metal piping systems that are likely to become energized must be bonded. This includes gas piping, compressed air lines, vacuum system piping, medical gas piping and the like. Bonding the piping systems ensures that if they become energized, then the overcurrent device supplying the circuit associated with these systems will trip.

Not all metal piping systems are likely to become energized, but many inspectors will require them to be bonded anyway. If a gas appliance is supplied with a branch circuit that contains an equipment grounding conductor, then the equipment grounding conductor in the branch circuit satisfies the required gas pipe bonding. If a gas appliance such as a gas water heater is not supplied with a branch circuit, then many feel the gas piping is not likely to become energized and therefore requires no additional bonding.

Section 250.104(B) takes all the permitted bonding methods from the previous paragraph and places them in a simple numbered format. The bonding conductor is sized from Table 250.122 using the rating of the circuit that is likely to energize the piping system. The metal piping system can be bonded to any of the following:

(1) Equipment grounding conductor for the circuit that is likely to energize the piping system

(2) Service equipment enclosure

(3) Grounded conductor at the service

(4) Grounding electrode conductor, if of sufficient size

(5) One or more grounding electrodes used

Below is a preview of the NEC®. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to NFPA 70.

2023 Code Language:

250.104(B) Other Metal Piping. If installed in or attached to a building or structure, a metal piping system(s), including gas piping, that is likely to become energized shall be bonded to any of the following:

(1) Equipment grounding conductor for the circuit that is likely to energize the piping system

(2) Service equipment enclosure

(3) Grounded conductor at the service

(4) Grounding electrode conductor, if of sufficient size

(5) One or more grounding electrodes used, if the grounding electrode conductor or bonding jumper to the grounding electrode is of sufficient size

The bonding conductor(s) or jumper(s) shall be sized in accordance with Table 250.122, and equipment grounding conductors shall be sized in accordance with Table 250.122 using the rating of the circuit that is likely to energize the piping system(s). The points of attachment of the bonding jumper(s) shall be accessible.

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

250.104(B) Bonding of Piping Systems and Exposed Structural Metal. Other Metal Piping.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

One of the following is NOT permitted to be used to bond the gas piping. Which of the following CANNOT be used to bond the gas piping system?

A: Grounding electrode conductor.
B: Service equipment enclosure.
C: A grounding electrode.
D: The intersystem bonding terminal.
Please register or sign in for electrical continuing education courses.

If you were already signed in, your session probably expired, please sign back in.