250.25 Grounding of Systems Permitted to Be Connected on the Supply Side of the Service Disconnect.

Many line side connections, such as this PV system, terminate in an enclosure that is not considered a service disconnect.
Click to Enlarge
Many line side connections, such as this PV system, terminate in an enclosure that is not considered a service disconnect.

Section 230.82 lists several items permitted to be connected to the supply side of an electrical service. These can include but are not limited to:

Most of the equipment mentioned above will connect to the service conductors and then terminate in some form of disconnect switch that is suitable for use as service equipment but not technically considered a “service” or a “service disconnect”.

NEC Article 250 has requirements for grounding and bonding of services and separately derived systems, but the items mentioned above do not meet the Article 100 definition of either, and yet they still require bonding and grounding.

Section 250.25 addresses grounding and bonding of supply-side disconnects that are not considered a service. Most of the language just points the code reader to other existing code sections where the requirements can be found.

Below is a preview of the NEC®. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to NFPA 70.

2023 Code Language:

250.25 Grounding of Systems Permitted to Be Connected on the Supply Side of the Service Disconnect. The grounding of systems connected on the supply side of the service disconnect, in accordance with 230.82, that are in enclosures separate from the service equipment enclosure shall comply with 250.25(A) or (B).

(A) Grounded System. If the utility supply system is grounded, the grounding of systems permitted to be connected on the supply side of the service disconnect and are installed in one or more separate enclosures from the service equipment enclosure shall comply with the requirements of 250.24(A) through (D).

(B) Ungrounded Systems. If the utility supply system is ungrounded, the grounding of systems permitted to be connected on the supply side of the service disconnect and are installed in one or more separate enclosures from the service equipment enclosure shall comply with the requirements of 250.24(E).

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

250.25 Grounding of Systems Permitted to Be Connected on the Supply Side of the Service Disconnect.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Based on the NEC, which of the following is true?

A: The rules in 250.25 apply to bonding services.
B: 250.25 pertains to grounding systems permitted to be connected on the supply side of the service disconnect.
C: 250.25 pertains to grounding on the load side of the service disconnect.
D: The rules in 250.25 apply to grounding services.
Please register or sign in for electrical continuing education courses.

If you were already signed in, your session probably expired, please sign back in.