705.12(A) Feeders.

Section 705.12(A)(2)(b) option 2 prohibits an overcurrent device at the load side of the power source connection point from being rated greater than the ampacity of the feeder.
Click to Enlarge
Section 705.12(A)(2)(b) option 2 prohibits an overcurrent device at the load side of the power source connection point from being rated greater than the ampacity of the feeder.

Code Change Summary: The language on source interconnections to feeders and feeder taps was restructured for clarity.

In the 2023 NEC®, the previous rules in 705.12(B)(1) and (2) were revised and relocated to 705.12(A).

Revised Section 705.12(A) is now specific only to parallel power production source connections to feeders and feeder taps. The rules in this section were formatted into a list but item 1 may see a revision in the 2026 NEC® to incorporate mandatory language like “shall be” rather than “is”.

Section 705.12(A)(2) and (3) describe specific installation methods.

The language in 705.12(A)(2) describes installations where the parallel power production source output connection is made to a feeder “at a location other than the opposite end of the feeder from the primary source overcurrent device”. For these installations, the portion of the feeder on the load side of the power source output connection shall be protected by one of the following:

  1. The feeder ampacity shall be not less than the sum of the rating of the primary source overcurrent device and 125% of the power-source output circuit current.
  2. An overcurrent device at the load side of the power source connection point shall be rated not greater than the ampacity of the feeder.

The language in 705.12(A)(3) describes installations where taps occur in accordance with 240.21(B)(2) or (B)(4). For these installations, the ampacity of tap conductors shall not be less than one-third of the sum of the rating of the overcurrent device protecting the feeder plus the ratings of any power source overcurrent devices connected to the feeder.

Below is a preview of the NEC®. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to the 2023 NEC® edition of NFPA 70.

2020 Code Language:

705.12(B)(1) Feeders. Where the power source output connection is made to a feeder, the feeder shall have an ampacity greater than or equal to 125% of the power-source output circuit current. Where the power-source output connection is made to a feeder at a location other than the opposite end of the feeder from the primary source overcurrent device, that portion of the feeder on the load side of the power source output connection shall be protected by one of the following:

  1. The feeder ampacity shall be not less than the sum of the primary source overcurrent device and 125% of the power-source output circuit current.
  2. An overcurrent device at the load side of the power source connection point shall be rated not greater than the ampacity of the feeder.

705.12(B)(2) Taps. Where power source output connections are made at feeders, all taps shall be sized based on the sum of 125% of all power source(s) output circuit current(s) and the rating of the overcurrent device protecting the feeder conductors for sizing tap conductors using the calculations in 240.21(B).

2023 Code Language:

705.12(A) Feeders and Feeder Taps. Where the power source output connection is made to a feeder, the following shall apply:

(1) The feeder ampacity is greater than or equal to 125% of the power-source output circuit current.

(2) Where the power-source output connection is made at a location other than the opposite end of the feeder from the primary source overcurrent device, that portion of the feeder on the load side of the power source output connection shall be protected by one of the following:

  1. The feeder ampacity shall be not less than the sum of the rating of the primary source overcurrent device and 125% of the power-source output circuit current.
  2. An overcurrent device at the load side of the power source connection point shall be rated not greater than the ampacity of the feeder.

(3) For taps sized in accordance with 240.21(B)(2) or (B)(4), the ampacity of taps conductors shall not be less than one-third of the sum of the rating of the overcurrent device protecting the feeder plus the ratings of any power source overcurrent devices connected to the feeder.

Did You Like This? Let Us Know With A Like! Thanks!

705.12(A) Feeders.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Based on the 2023 NEC, which of the following is true of 705.12(A)(2)?

A: It applies to installations where the power-source output connection is made at a location other than the opposite end of the feeder from the primary source overcurrent device.
B: The feeder ampacity must be equal to 100% of the dc power-source output rating.
C: The feeder ampacity must be greater than 100% of the dc power-source output rating.
D: The feeder ampacity must be greater than or equal to 100% of the dc power-source output rating.