517.13 Equipment Grounding Conductor for Receptacles and Fixed Electrical Equipment in Patient Care Spaces.

Wiring serving patient care spaces shall comply with the requirements of 517.13(A) and (B).
Click to Enlarge
Wiring serving patient care spaces shall comply with the requirements of 517.13(A) and (B).

Code Change Summary: Changes were made to bring clarity to wiring serving patient care spaces.

In the 2023 NEC®, the parent text in Section 517.13 was modified to make it clear that the equipment grounding requirements of 517.13(A) and (B) apply to wiring serving the patient care space rather than only the wiring in the patient care space.

Even though the previous language in the parent text of 517.13 required wiring in patient care spaces to comply with 517.13(A) and (B), the actual equipment grounding requirements in 517.13(A) still applied to all branch circuits serving patient care spaces.

Article 100 makes it clear that a branch circuit includes all circuit conductors between the final overcurrent device protecting the circuit and the outlets.

The change in the parent text makes clear that the equipment grounding requirements in 517.13(A) and (B) apply to the entire branch circuit even if only a small portion of it enters the patient care space.

Another important change was the relocation of 517.13(B) exception 2 to the appropriate location which is 517.13(A). This exception permits luminaires higher than 7-1/2 feet above the floor and switches located outside of the patient care vicinity to be connected to an equipment grounding return path complying with the requirements of 517.13(A) or (B).

Moving the exception will help the code reader to apply the language correctly.

Below is a preview of the NEC®. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to the 2023 NEC® edition of NFPA 70.

2020 Code Language:

517.13 Equipment Grounding Conductor for Receptacles and Fixed Electrical Equipment in Patient Care Spaces. Wiring in patient care spaces shall comply with 517.13(A) and (B).

2023 Code Language:

517.13 Equipment Grounding Conductor for Receptacles and Fixed Electrical Equipment in Patient Care Spaces. Wiring serving patient care spaces shall comply with the requirements of 517.13(A) and (B).

Exception: Luminaires more than 7-1/2 feet above the floor and switches located outside of the patient care vicinity shall be permitted to be connected to an equipment grounding return path complying with the requirements of 517.13(A) or (B).

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

517.13 Equipment Grounding Conductor for Receptacles and Fixed Electrical Equipment in Patient Care Spaces.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Based on the 2023 NEC, which of the following is true?

A: The equipment grounding requirements in 517.13(A) and (B) apply to the entire branch circuit even if only a small portion of it enters the patient care space.
B: Only the portion of the wiring inside the patient care space is required to comply with the requirements of 517.13(A) and (B).
C: Wiring serving hospital corridors shall comply with the requirements of 517.13(A) and (B).
D: Wiring serving hospital waiting rooms shall comply with the requirements of 517.13(A) and (B).
Please register or sign in for electrical continuing education courses.

If you were already signed in, your session probably expired, please sign back in.