110.17 Servicing and Maintenance of Equipment.

Using OEM replacement parts is one option for equipment that requires repair during servicing.
Click to Enlarge
Using OEM replacement parts is one option for equipment that requires repair during servicing.

Code Change Summary: A new code section was added to address servicing and maintenance of equipment.

In the 2023 NEC®, Article 100 received a new definition of the word “servicing” which defines what it is. Section 110.17, also new in the 2023 NEC®, provides guidelines on how servicing must be performed and who should do it.

This new section corresponds with similar efforts to define and provide requirements for reconditioning of equipment, which differs from routine servicing or maintenance. Terminology for the new code section aligns with requirements in NFPA 70B which is the Recommended Practice for Electrical Equipment Maintenance.

Section 110.17 only allows qualified persons trained in servicing and maintenance of equipment to perform these activities. In addition, servicing and preventive maintenance must be in line with the original equipment manufacturer’s instructions, as well as information included in the product listing information, applicable industry standards, or as approved by the inspection authority.

This new section also provides three options for selecting replacement parts during service or maintenance which can be difficult when original equipment manufacturer (OEM) parts are obsolete:

  1. Replacement parts can be provided by the original equipment manufacturer.
  2. Replacement parts can be designed by an engineer experienced in the design of replacement parts for the type of equipment being serviced or maintained.
  3. Replacement parts can be approved by the authority having jurisdiction.

Below is a preview of the NEC®. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to the 2023 NEC® edition of NFPA 70.

2020 Code Language:

This code section did not exist.

2023 Code Language:

N 110.17 Servicing and Maintenance of Equipment. Servicing and electrical preventive maintenance shall be performed by qualified persons trained in servicing and maintenance of equipment and shall comply with the following:

(1) The servicing and electrical preventive maintenance shall be performed in accordance with the original equipment manufacturer’s instructions and information included in the listing information, applicable industry standards, or as approved by the authority having jurisdiction.

(2) The servicing and electrical preventive maintenance shall be performed using identified replacement parts that are verified under applicable product standards. The replacement parts shall comply with at least one of the following:

  1. Be provided by the original equipment manufacturer
  2. Be designed by an engineer experienced in the design of replacement parts for the type of equipment being serviced or maintained
  3. Be approved by the authority having jurisdiction

 

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

110.17 Servicing and Maintenance of Equipment.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Based on the 2023 NEC, which of the following is an option for selecting replacement parts during routine servicing of electrical equipment?

A: Obtain replacement parts from the salvage yard.
B: Obtain replacement parts from the original equipment manufacturer.
C: Replacement parts can be approved by the general contractor.
D: Replacement parts can be designed by the general contractor.
Please register or sign in for electrical continuing education courses.

If you were already signed in, your session probably expired, please sign back in.