Ampacity Table 310.16.

This is a portion of NEC Table 310.16. At the bottom of the table is the following note: *Refer to 240.4(D) for conductor overcurrent protection limitations.
Click to Enlarge
This is a portion of NEC Table 310.16. At the bottom of the table is the following note: *Refer to 240.4(D) for conductor overcurrent protection limitations.

When using conductor ampacity Table 310.16, it is important to understand why some conductor sizes on the table have an asterisk (*). Conductor sizes 18 AWG through 10 AWG are considered “small conductors” and are subject to the rules for small conductors in 240.4(D).

Section 240.4(D) states the following:

Small Conductors. Unless specifically permitted in 240.4(E) or (G), the overcurrent protection shall not exceed that required by 240.4(D)(1) through (D)(8) after any correction factors for ambient temperature and number of conductors have been applied.

This section is where the all too familiar rules come from that require no larger than a 15 amp overcurrent device to protect a 14 AWG copper conductor, or a 20 amp max overcurrent device to protect a 12 AWG copper conductor, or a 30 amp max overcurrent device to protect a 10 AWG copper conductor. These values are generally true unless specifically permitted in 240.4(E) or (G).

Section 240.4(D) has nothing to do with the actual rating of the wire but everything to do with the maximum allowable fuse or circuit breaker used to protect the wire. Many electricians have confused these rules and think a type THWN, 10 AWG copper wire is only rated at 30 amps when in fact it is rated to carry 35 amps according to Table 310.16 but in most cases a fuse or circuit breaker installed to protect the wire is not permitted to be larger than 30 amps as stated in 240.4(D).

See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to NFPA 70.

Did You Like This? Let Us Know With A Like! Thanks!

Ampacity Table 310.16.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Which of the following is true for a type THWN, 12 AWG copper conductor?

A: It has a maximum rating of 20 amps.
B: It has a maximum rating of 30 amps.
C: It has a maximum rating of 25 amps.
D: It has a maximum rating of 15 amps.
Please register or sign in for electrical continuing education courses.

If you were already signed in, your session probably expired, please sign back in.