When installing insulated conductors of 4 AWG or larger, the minimum dimensions of pull or junction boxes installed in a raceway or cable run must comply with 314.28(A)(1) through (A)(3).
The rules apply to “insulated” conductors for a reason. When installing large insulated conductors, care must be taken to ensure that the conductor insulation is not compromised during the wire pull because the box is too small.
Section 314.28(A)(1) provides the minimum required dimension for an enclosure containing a straight pull (see image). For a straight pull, the length of the box or conduit body shall not be less than eight times the trade size of the largest raceway.
The width of the box used for the straight pull is not specified. It just needs to be wide enough for the conduit entry in order to be able to spin the lock nut on.
See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to NFPA 70.
What is the minimum length required for an enclosure used for a straight pull containing 3/0 copper, insulated conductors that enter and leave through 2.5 inch conduits?
Please register or sign in for electrical continuing education courses. If you were already signed in, your session probably expired, please sign back in. |