OESC 702.4 Capacity and Rating.

For one- and two-family dwellings in Oregon, manual management of the connected load is permitted.
Click to Enlarge
For one- and two-family dwellings in Oregon, manual management of the connected load is permitted.

When it comes to optional standby systems, the NEC® is clear that if using an automatic transfer switch, the standby system must be either capable of supplying the full load or there must be a load management system for the standby system.

This language has been amended in Oregon and now reads as follows:

702.4(A) System Capacity.

(1) Manual and Nonautomatic Load Connection. If the connection of load is manual or nonautomatic, an optional standby system shall have adequate capacity and rating for the supply of all equipment intended to be operated at one time. The user of the optional standby system shall be permitted to select the load connected to the system.

(2) Automatic Load Connection. If the connection of load is automatic, an optional standby system shall comply with 702.4(A)(2)(a) or (A)(2)(b) in accordance with Parts I through IV of Article 220 or by another approved method.

(a) Full Load. The standby source shall be capable of supplying the full load that is automatically connected.

(b) Energy Management System (EMS). Where a system is employed in accordance with 750.30 that will automatically manage the connected load, the standby source shall have a capacity sufficient to supply the maximum load that will be connected by the EMS.

Exception: In one- and two-family dwellings manual management of the connected load shall be permitted.

Oregon amendments to the 2023 NEC® are located in “Table 1-E” of the Oregon Electrical Specialty Code (OESC) which can be seen using the following link or the OESC PDF file located near the bottom of the screen: 2023 OESC

  Click here to view the OESC  

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

OESC 702.4 Capacity and Rating.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Which of the following is true for an optional standby generator for a single family dwelling?

A: Management of the connected load shall be performed only by load shedding equipment.
B: Manual management of the connected load shall be permitted.
C: The standby generator shall be capable of supplying the full load of the entire dwelling during peak demand.
D: Overcurrent devices for the system shall be selectively coordinated for .01 seconds and greater.
Please register or sign in for electrical continuing education courses.