406.9(B) Receptacles in Wet Locations.

This outlet box hood is identified as extra duty. On the right side it states that the cover is suitable for wet locations when the cover is closed.
Click to Enlarge
This outlet box hood is identified as extra duty. On the right side it states that the cover is suitable for wet locations when the cover is closed.

Code Change Summary: Revisions were made for receptacles requiring an extra duty outlet box hood.

For several code cycles, outlet box hoods, also called in-use covers or bubble covers, have been required for 15- and 20-ampere, 125- and 250-volt receptacles installed in wet locations. They must also be weatherproof whether or not the attachment plug cap is inserted. In the 2011 NEC®, these types of covers were only required to be listed and identified as “extra duty” for other than one- or two-family dwellings and only if installed on an enclosure supported from grade as described in 314.23(B) or 314.23(F). Outlet box hoods used for receptacles in wet locations of one- or two-family dwellings were not required by this code section to be listed or built extra duty.

In the 2014 NEC®, the rules have changed. The rules are no longer different depending on if the receptacles are used in wet locations of dwellings or commercial use, or if the receptacles are mounted on a post supported from grade versus wall mounted. As well, all of these types of outlet box hoods must be listed and identified as “extra duty”.

These covers take a lot of abuse and requiring them to be listed for heavy duty purposes will hopefully ensure that the cover remains in place for years.

Below is a preview of the NEC®.  See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on the “free access” tab and select the applicable year of NFPA 70 (National Electrical code).

2011 Code language:

406.9(B)(1) 15- and 20-Ampere Receptacles in a Wet Location. 15- and 20-ampere, 125- and 250-volt receptacles installed in a wet location shall have an enclosure that is weatherproof whether or not the attachment plug cap is inserted. For other than one- or two-family dwellings, an outlet box hood installed for this purpose shall be listed, and where installed on an enclosure supported from grade as described in 314.23(B) or as described in 314.23(F) shall be identified as “extra-duty.” All 15- and 20-ampere, 125- and 250-volt nonlocking-type receptacles shall be listed weather-resistant type.

2014 Code Language including the correction from the errata:

406.9(B)(1) Receptacles of 15 and 20 Amperes in a Wet Location. Receptacles of 15 and 20 amperes, 125 and 250 volts installed in a wet location shall have an enclosure that is weatherproof whether or not the attachment plug cap is inserted. An outlet box hood installed for this purpose shall be listed and shall be identified as “extra duty.” All 15- and 20-ampere, 125- and 250-volt nonlocking-type receptacles shall be listed weather-resistant type.

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

406.9(B) Receptacles in Wet Locations.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Which of the following is true of an outlet box hood for a 20-ampere, 125-volt receptacle installed in a wet location?

A: The outlet box hood shall be listed and identified as “extra duty”.
B: The outlet box hood must be identified as “extra duty” only for commercial applications.
C: The enclosure must be weatherproof only when the attachment plug cap is inserted.
D: The enclosure must be weatherproof only when the attachment plug cap is removed.