Emergency Illumination.

A single LED emergency luminaire above an exit door. Is it compliant with 700.16(B)?
Click to Enlarge
A single LED emergency luminaire above an exit door. Is it compliant with 700.16(B)?

In 1956, the NEC® required emergency illumination to be “designed and installed that the failure of any individual lighting element, such as the burning out of a light bulb, cannot leave any space in total darkness”. Over time, that language evolved into “emergency lighting systems shall be designed and installed so that the failure of any illumination source cannot leave in total darkness any space that requires emergency illumination.

From the 1956 code language, it’s clear that the original idea was to address the short life of a common incandescent light bulb. Newer technology has brought fluorescent emergency luminaires with ballasts and LED luminaires powered by drivers into the spotlight and with it come many questions for the designer, installer, and inspector:

The current NEC® code language is a step closer but still doesn’t answer all of the questions. In the 2020 NEC®, the phrase “individual lighting element” was replaced with “illumination source” and the example of “such as the burning out of a lamp” was removed so as not to narrow down the possibilities of what an “illumination source” may apply to.

It is likely that this code section will see further revisions in the future.

Become familiar with the above concept and what the code is trying to accomplish. There can be a huge delay if during the final inspection, the inspector finds several areas of the building where the failure of an individual lighting source such as the burning out of an emergency luminaire lamp can result in the area requiring the illumination to be left in total darkness.

Below is a preview of the NEC® (NFPA 70). See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to the edition of the NEC® being enforced.

NEC 700.16 Emergency Illumination.

(A) General. Emergency illumination shall include means of egress lighting, illuminated exit signs, and all other luminaires specified as necessary to provide required illumination.

(B) System Reliability. Emergency lighting systems shall be designed and installed so that the failure of any illumination source cannot leave in total darkness any space that requires emergency illumination...

(C) Discharge Lighting. Where high-intensity discharge lighting such as high- and low-pressure sodium, mercury vapor, and metal halide is used as the sole source of normal illumination, the emergency lighting system shall be required to operate until normal illumination has been restored.

(D) Disconnecting Means. Where an emergency system is installed, emergency illumination shall be provided in the area of the disconnecting means required by 225.31 and 230.70, as applicable, where the disconnecting means are installed indoors.

Exception: Alternative means that ensure that the emergency lighting illumination level is maintained shall be permitted.

Did You Like This? Let Us Know With A Like! Thanks!

Emergency Illumination.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Based on the NEC, which of the following is true?

A: Emergency lighting systems shall be designed and installed so that the failure of any illumination source cannot leave in total darkness any space that requires emergency illumination.
B: All lighting systems shall be designed and installed so that the failure of a ballast cannot leave any area in total darkness.
C: LED luminaires are not permitted to be used for emergency illumination.
D: Fluorescent luminaires are not permitted to be used for emergency illumination.
Please register or sign in for electrical continuing education courses.

If you were already signed in, your session probably expired, please sign back in.