392.44 Expansion Splice Plates.

An expansion splice plate may have slotted holes to allow for movement in the cable tray. A bonding jumper is required where cable tray systems are mechanically discontinuous.
Click to Enlarge
An expansion splice plate may have slotted holes to allow for movement in the cable tray. A bonding jumper is required where cable tray systems are mechanically discontinuous.

Code Change Summary: New code section with requirements for expansion splice plates in a cable tray.

In the 2020 NEC® a public input (code change proposal) was accepted to add requirements for thermal expansion and contraction in a spliced cable tray. There are no specific measurements or calculations provided in the NEC® to determine if or how many expansion splice plates are required but the installation instructions for the cable tray should provide guidance.

Another helpful document is NEMA Publication VE 2-2013 Cable Tray Installation Guidelines. According to the document, there are four basic types of cable tray connectors including rigid, expansion, adjustable, and reducer. In the NEMA document, table 3.2 provides the Maximum Spacing between Expansion Joints that Provide for 250 mm (1 in) Movement. Additionally, the document states:

“Special hardware is supplied with expansion splice plates. The nuts may have a stopping device (plastic stop nut). Important: For plastic stop nut designs, tighten hardware, then loosen 1/2 turn”.

Below is a preview of the NEC®. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to the 2020 NEC® edition of NFPA 70.

2017 Code Language:

This code section did not exist.

2020 Code Language:

N 392.44 Expansion Splice Plates. Expansion splice plates for cable trays shall be provided where necessary to compensate for thermal expansion and contraction.

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

392.44 Expansion Splice Plates.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Based on the 2020 NEC, which of the following is true?

A: Expansion splice plates shall be listed.
B: Expansion splice plates for cable trays shall be provided where the temperature difference exceeds 10 degrees.
C: Expansion splice plates for cable trays shall be provided every 10 feet.
D: Expansion splice plates for cable trays shall be provided where necessary to compensate for thermal expansion and contraction.
Please register or sign in for electrical continuing education courses.

If you were already signed in, your session probably expired, please sign back in.