110.9 Interrupting Rating.

The interupting rating of an overcurrent device is generally its AIC rating. The interrupting rating of a passive device such as a lighting contactor is the amount of current that the contactor is rated to interrupt.
Click to Enlarge
The interupting rating of an overcurrent device is generally its AIC rating. The interrupting rating of a passive device such as a lighting contactor is the amount of current that the contactor is rated to interrupt.

Code Change Summary: Revised wording about the requirements for equipment interrupt ratings.

This code section addresses two different types of equipment and how they must be rated:

Before an electrician purchases or installs the items mentioned above, care should be taken to ensure that the equipment selected is properly rated for the current that must be interrupted. Overcurrent devices must have an interrupting rating sufficient for the current that is available at the line terminals. This is the maximum available fault current. For example, If it is determined that there is 9,900 amps of available fault current at the line terminals of a 200 amp circuit breaker, using a breaker with a 10k AIC rating (10,000 amps interrupt capacity) complies with 110.9.

Devices that do not interrupt current at fault levels (switches and contactors) just need to have an interrupt rating sufficient for the current that needs to be interrupted. For example, to interrupt 30 amps of lighting load, use a contactor that is rated for at least 30 amps.

Below is a preview of the NEC®.  See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on the “free access” tab and select the applicable year of NFPA 70 (National Electrical code).

2011 Code Language:

110.9 Interrupting Rating. Equipment intended to interrupt current at fault levels shall have an interrupting rating not less than the nominal circuit voltage and the current that is available at the line terminals of the equipment. Equipment intended to interrupt current at other than fault levels shall have an interrupting rating at nominal circuit voltage not less than the current that must be interrupted.

2014 Code Language:

110.9 Interrupting Rating. Equipment intended to interrupt current at fault levels shall have an interrupting rating at nominal circuit voltage sufficient for the current that is available at the line terminals of the equipment. Equipment intended to interrupt current at other than fault levels shall have an interrupting rating at nominal circuit voltage sufficient for the current that must be interrupted.

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

110.9 Interrupting Rating.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Which of the following circuit breakers can be used at a location in the wiring system where there is 38,000 amps of available fault current?

A: A 50 amp breaker with a 36k AIC rating.
B: A 50 amp breaker with a 42k AIC rating.
C: A 50 amp breaker with a 10k AIC rating.
D: A 50 amp breaker with a 22k AIC rating.
Please register or sign in for electrical continuing education courses.