250.194 Grounding and Bonding of Fences and Other Metal Structures.

Some substations are privately owned and covered by the NEC. For these, bonding of the fences is covered in 250.194.
Click to Enlarge
Some substations are privately owned and covered by the NEC. For these, bonding of the fences is covered in 250.194.

Code Change Summary: A new code section was added in part X of Article 250 to address grounding and bonding of fences and other metal structures related to substations.

Section 250.194 is new in Part X of Article 250 and covers the grounding and bonding requirements for metal structures and fences near a substation. Most substations are utility owned and therefore not covered in the NEC® but once in a while, a substation is privately owned and the NEC® applies.

The new code section requires fencing to be bonded to the grounding electrode system if the fencing is within 16 ft. of any exposed electrical conductors or equipment. For these fences, a wire type bonding jumper is required as follows:

Below is a preview of the NEC®.  See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on the “free access” tab and select the applicable year of NFPA 70 (National Electrical code).

2014 Code Language:

250.194 Grounding and Bonding of Fences and Other Metal Structures.

Metallic fences enclosing, and other metal structures in or surrounding, a substation with exposed electrical conductors and equipment shall be grounded and bonded to limit step, touch, and transfer voltages.

(A) Metal Fences. Where metal fences are located within 5 m (16 ft) of the exposed electrical conductors or equipment, the fence shall be bonded to the grounding electrode system with wire-type bonding jumpers as follows:

(1) Bonding jumpers shall be installed at each fence corner and at maximum 50 m (160 ft) intervals along the fence.

(2) Where bare overhead conductors cross the fence, bonding jumpers shall be installed on each side of the crossing.

(3) Gates shall be bonded to the gate support post, and each gate support post shall be bonded to the grounding electrode system.

(4) Any gate or other opening in the fence shall be bonded across the opening by a buried bonding jumper.

(5) The grounding grid or grounding electrode systems shall be extended to cover the swing of all gates.

(6) The barbed wire strands above the fence shall be bonded to the grounding electrode system.

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

250.194 Grounding and Bonding of Fences and Other Metal Structures.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

When does the NEC require fencing surrounding a substation be bonded to the grounding electrode system?

A: When the fencing is within 17 ft. of enclosed electrical equipment.
B: When the substation is owned by the utility company.
C: When the fencing is within 16 ft. of exposed electrical conductors or equipment.
D: When the closest overhead power line is 20 ft. from the perimeter fencing.
Please register or sign in for electrical continuing education courses.