Class 1, Class 2, and Class 3 Remote-Control, Signaling, and Power-Limited Circuits.

Type CL2R/CL3R cable can be used for both Class 2 and 3 circuits and installed in riser applications (vertical runs penetrating one or more floors and in vertical runs in a shaft).
Click to Enlarge
Type CL2R/CL3R cable can be used for both Class 2 and 3 circuits and installed in riser applications (vertical runs penetrating one or more floors and in vertical runs in a shaft).

NFPA 731 Section 4.6.3.1 requires the installation of all wiring, cable, and equipment to be performed in accordance with NFPA 70 (NEC), Article 725 or Article 800, where applicable.

NEC Article 725 covers Class 1, Class 2, and Class 3 remote-control, signaling, and power-limited circuits which are often used in a security system. NEC® Article 800 covers communications systems such as phone lines which are often used to alert security monitoring companies of a potential breach in the system.

NEC Article 100 defines each of the different circuit types covered in Article 725.

Below is a sample of NFPA 731. For the complete section, see the actual NFPA 731 text at NFPA.ORG. Once there, click on the free access link to the the latest edition of NFPA 731.

4.6.3 Wiring.

4.6.3.1 The installation of all wiring, cable, and equipment shall be performed in accordance with NFPA 70, Article 725 or Article 800, where applicable.

Below is a sample of the NEC®. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to the latest NEC® edition of NFPA 70.

Article 100 Definitions:

Class 1 Circuit. The portion of the wiring system between the load side of the overcurrent device or power-limited supply and the connected equipment.

Informational Note: See 725.41 for voltage and power limitations of Class 1 circuits.

Class 2 Circuit. The portion of the wiring system between the load side of a Class 2 power source and the connected equipment. Due to its power limitations, a Class 2 circuit is considered safe from a fire initiation standpoint and provides acceptable protection from electric shock.

Class 3 Circuit. The portion of the wiring system between the load side of a Class 3 power source and the connected equipment. Due to its power limitations, a Class 3 circuit considers safety from a fire initiation standpoint. Since higher levels of voltage and current than for Class 2 are permitted, additional safeguards are specified to provide protection from an electric shock hazard that could be encountered.

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

Class 1, Class 2, and Class 3 Remote-Control, Signaling, and Power-Limited Circuits.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Which of the following is true regarding Class 1, 2 or 3 circuits?

A: Class 1 circuits are considered safe from a fire initiation standpoint.
B: Class 1 circuits are considered safe from electric shock.
C: Class 2 circuits are considered safe from a fire initiation standpoint and provides acceptable protection from electric shock.
D: Class 3 circuits are considered safe from a fire initiation standpoint and electric shock.
Please register or sign in for electrical continuing education courses.

If you were already signed in, your session probably expired, please sign back in.