440.10 HVAC Multimotor and Combination-Load Equipment. Short-Circuit Current Rating.

Now that the calculation has been performed, the inspector can verify that the correct conductor size, length and type has been installed in order to get the available short circuit current down to 5,000 amps to match the SCCR on the control panel.
Click to Enlarge
Now that the calculation has been performed, the inspector can verify that the correct conductor size, length and type has been installed in order to get the available short circuit current down to 5,000 amps to match the SCCR on the control panel.

Most multimotor and combination-load equipment is already required by Section 440.4(B) to be marked with a short-circuit current rating (SCCR). The intent is so that the electrician and inspector can ensure compliance with NEC® 110.9 and 110.10.

The only way to ensure the HVAC equipment is rated to handle the amount of short circuit current available is to first find out the maximum amount of Available Fault Current that could be delivered to the equipment during a short circuit condition and then to determine the SCCR of the equipment by looking at the nameplate. As long as the HVAC equipment has a SCCR equal to or greater than the available short circuit current, then the installation complies with NEC® 110.10.

In the 2017 NEC®, language requires motor controllers of multimotor and combination-load equipment to be installed in a location where the available short-circuit current does not exceed the SCCR of the equipment. As well, new subsection B states: “When motor controllers or industrial control panels of multimotor and combination load equipment are required to be marked with a short circuit current rating, the available short circuit current and the date the short circuit current calculation was performed shall be documented and made available to those authorized to inspect the installation”.

Knowing the amount of available short circuit current at the HVAC equipment is the first step in ensuring that the HVAC equipment is properly rated for the worst-case fault condition that it may see.

See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on the “free access” tab and select the applicable year of NFPA 70 (National Electrical code).

2014 Code Language:

440.10 This code section does not exist.

2017 Code Language:

440.10 Short-Circuit Current Rating.

(A) Installation. Motor controllers of multimotor and combination-load equipment shall not be installed where the available short-circuit current exceeds its short-circuit current rating as marked in accordance with 440.4(B).

(B) Documentation. When motor controllers or industrial control panels of multimotor and combination load equipment are required to be marked with a short circuit current rating, the available short circuit current and the date the short circuit current calculation was performed shall be documented and made available to those authorized to inspect the installation.

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

440.10 HVAC Multimotor and Combination-Load Equipment. Short-Circuit Current Rating.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Which of the following is true for HVAC multimotor and combination load equipment with a marked short-circuit current rating?

A: It must also have an available fault current rating.
B: It shall not be installed where the available fault current is less than its interrupt rating.
C: Installing a unit with a 10kA SCCR at a location where where the available short-circuit current is 12kA would be a code violation.
D: It must be installed where the available fault current exceeds its short-circuit current rating.
Please register or sign in for electrical continuing education courses.

If you were already signed in, your session probably expired, please sign back in.