230.30(B) Underground Service Conductors. Wiring Methods.

Obviously these small raceways are not service entrance conductor raceways. If these raceways were 24 inches deep and contained service entrance conductors, would this warning ribbon be placed correctly? Hint: 300.5(D)(3).
Click to Enlarge
Obviously these small raceways are not service entrance conductor raceways. If these raceways were 24 inches deep and contained service entrance conductors, would this warning ribbon be placed correctly? Hint: 300.5(D)(3).

Code Change Summary: New code language was added to specifically address the wiring methods permitted for underground service conductors.

Prior to the code change, Part III of Article 230 never mentioned what types of wiring methods could be used for underground service conductors. Now, Part III names all of the wiring methods permitted to be used for underground service conductors.

Without the code change, the user would search through Part IV or Article 230 which applies generally to all service conductors, whether overhead or underground, and select a wiring method that could be used underground based on practicality.

For example, in the 2011 NEC®, Part IV of Article 230 would allow open wiring on insulators to be used for service conductors but an experienced electrician knows that open wiring on insulators cannot be installed underground, which by default means that the open wiring on insulators can only be used for overhead service conductors.

Now, wiring methods that cannot be used underground are not even mentioned in the new code language that pertains to underground service conductors.

Below is a preview of the NEC®.  See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on the “free access” tab and select the applicable year of NFPA 70 (National Electrical code).

2014 Code Language:

230.30(B) Wiring Methods. Underground service conductors shall be installed in accordance with the applicable requirements of this Code covering the type of wiring method used and shall be limited to the following methods:

(1) Type RMC conduit

(2) Type IMC conduit

(3) Type NUCC conduit

(4) Type HDPE conduit

(5) Type PVC conduit

(6) Type RTRC conduit

(7) Type IGS cable

(8) Type USE conductors or cables

(9) Type MV or Type MC cable identified for direct burial applications

(10) Type MI cable, where suitably protected against physical damage and corrosive conditions.

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

230.30(B) Underground Service Conductors. Wiring Methods.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

One of the following CANNOT be used as a wiring method for underground service conductors. Which of the following CANNOT be used as a wiring method for underground service conductors?

A: RMC.
B: IMC.
C: NUCC.
D: Open wiring on insulators.
Please register or sign in for electrical continuing education courses.