250.104(B) Bonding other metal piping.

Rule 871. Section 250.104(B) of the code is amended to read as follows:

250.104(B). Bonding other metal piping.

(1) Other metal piping. If installed in or attached to a building or structure, a metal piping system, including gas piping, capable of becoming energized shall be bonded to any of the following:

(a) Equipment grounding conductor for the circuit that is likely to energize the piping system.

(b) Service equipment enclosure.

(c) Grounded conductor at the service.

(d) Grounding electrode conductor, if of sufficient size.

(e) One or more grounding electrodes used, if the grounding electrode conductor or bonding jumper to the grounding electrode is of sufficient size. The bonding conductor or conductors, or the jumper or jumpers shall be sized in accordance with table 250.122, and equipment grounding conductors shall be sized in accordance with table 250.122 using the rating of the circuit that is likely to energize the piping system or systems. The points of attachment of the bonding jumper or jumpers shall be accessible.

(2) Corrugated stainless steel tubing (CSST). Listed corrugated stainless steel tubing gas piping systems shall be bonded to the electrical service grounding electrode system. The bonding jumper shall connect to a metallic pipe or fitting between the point of delivery and the first downstream CSST fitting. The bonding jumper shall be not smaller than 6 AWG copper wire or equivalent. A gas piping system that is bonded pursuant to this section shall be considered effectively bonded regardless of the amount of CSST in the system.

Exception: Listed CSST piping systems approved for installation without additional bonding by the manufacturer.

This amendment helps to provide consistency in Michigan since each different manufacturer of CSST has their own rules on how to and what size bond wire must be used to bond the CSST.

Refer to the Department of Licensing and Regulatory Affairs 2023 Michigan electrical code rules part 8 to answer the question below.

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

250.104(B) Bonding other metal piping.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

According to Michigan’s amendment to NEC section 250.104(B), what is the minimum size conductor required to bond CSST to a grounded conductor at the service?

A: 8 AWG copper.
B: 6 AWG copper.
C: 4 AWG copper.
D: 10 AWG copper.
Please register or sign in for electrical continuing education courses.

If you were already signed in, your session probably expired, please sign back in.