440.9 Grounding and Bonding.

Even though EMT is recognized as an equipment grounding conductor, if installed outdoors on a rooftop to serve multimotor and combination-load equipment, it now requires a wire type equipment grounding conductor in the raceway.
Click to Enlarge
Even though EMT is recognized as an equipment grounding conductor, if installed outdoors on a rooftop to serve multimotor and combination-load equipment, it now requires a wire type equipment grounding conductor in the raceway.

Code Change Summary: A new code section was added to address HVAC equipment grounding and bonding when metal raceways are involved.

Several public inputs were submitted this code cycle to require a wire type equipment grounding conductor for rooftop HVAC equipment. There are many types of equipment grounding conductors permitted in 250.118 ranging from a wire type conductor to using certain types of metal raceways as the actual equipment grounding path.

Electrical metallic tubing (EMT) is one type of acceptable equipment grounding conductor listed in Section 250.118. When installed properly and the fittings are made up wrench-tight, EMT is an excellent equipment grounding conductor.

For the 2017 NEC®, a new section was added to address proper equipment grounding of multimotor and combination-load equipment installed outdoors on rooftops. Most rooftop air conditioners and other types of HVAC equipment are considered multimotor and combination-load equipment due to the nature of the equipment and multiple loads incorporated into each unit.

The new code section states: Where multimotor and combination-load equipment is installed outdoors on a roof, an equipment grounding conductor of the wire type shall be installed in outdoor portions of metallic raceway systems that use non-threaded fittings.

The intent is to address a common occurrence where a non-threaded raceway such as EMT is installed and the fittings either come loose or were never made up wrench-tight to begin with. In this case, the equipment grounding path is compromised and the metal raceway may not provide a reliable return path during a ground-fault condition.

Below is a preview of the NEC®. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to the 2017 NEC® edition of NFPA 70.

2017 Code Language:

N 440.9 Grounding and Bonding. Where multimotor and combination-load equipment is installed outdoors on a roof, an equipment grounding conductor of the wire type shall be installed in outdoor portions of metallic raceway systems that use non-threaded fittings.

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

440.9 Grounding and Bonding.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Which of the following is true for outdoor rooftop mounted multimotor and combination-load equipment?

A: The outdoor branch circuit raceway using non-threaded fittings can serve as the equipment grounding conductor.
B: The outdoor feeder raceway using non-threaded fittings can serve as the equipment grounding conductor.
C: A plastic raceway using non-threaded fittings can serve as the equipment grounding conductor.
D: A wire type equipment grounding conductor shall be installed in outdoor portions of metallic raceway systems that use non-threaded fittings.
Please register or sign in for electrical continuing education courses.

If you were already signed in, your session probably expired, please sign back in.