400.12 Uses Not Permitted.

Many ceiling mounted projectors are installed incorrectly with the flexible projector cord penetrating the ceiling tile to plug into an above grid receptacle. This recessed box is plenum rated and creates a code compliant way to plug in the projector without the flexible cord being exposed in the space above the suspended ceiling.
Click to Enlarge
Many ceiling mounted projectors are installed incorrectly with the flexible projector cord penetrating the ceiling tile to plug into an above grid receptacle. This recessed box is plenum rated and creates a code compliant way to plug in the projector without the flexible cord being exposed in the space above the suspended ceiling.

Code Change Summary: A new exception for flexible cords and flexible cables was added to note 5 under 400.12 (uses not permitted).

Section 400.10 now specifies the uses permitted for flexible cords and flexible cables while 400.12 provides the uses NOT permitted. These requirements were previously found in 400.7 and 400.8 of the 2014 NEC®. More importantly, in the 2017 NEC®, a new exception was added to note 5 under 400.12 (uses not permitted).

Note 5 states that flexible cables, flexible cord sets, and power supply cords shall not be used where “concealed by walls, floors, or ceilings or located above suspended or dropped ceilings”. The new exception now allows it, if contained within an enclosure for use in “Other Spaces Used for Environmental Air” as permitted by 300.22(C)(3).

When Section 300.22(C) speaks of “Other Spaces Used for Environmental Air” it means spaces not specifically fabricated for environmental air-handling purposes but used for air-handling purposes as a plenum.

Plenums sometimes exist in the space above a suspended ceiling where an air conditioner may be present.

Here are two rules to determine if the space above a grid ceiling is a plenum:

Wiring methods permitted from 300.22(C) in a plenum are generally limited to metal cables, metal boxes, metal raceways and certain nonmetallic jacketed plenum rated cables with low smoke and heat release properties. The idea is to make sure that if an above ceiling cable melts, the smoke released back into the return air, and recirculated back into the building supply air system is not dense enough to block emergency lights and exit signs from being seen by building occupants during egress.

The new exception to 400.12(5) basically allows a flexible cord to be installed above a suspended ceiling as long as it is contained within an enclosure that is either made of metal or it can be nonmetallic as long as it is listed for use within plenum and has low smoke and heat release properties.

Below is a preview of Article 400. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to the 2017 NEC® edition of NFPA 70.

2014 Code Language:

400.8 Uses Not Permitted. Unless specifically permitted in 400.7, flexible cords and cables shall not be used for the following:

(1) As a substitute for the fixed wiring of a structure

(2) Where run through holes in walls, structural ceilings, suspended ceilings, dropped ceilings, or floors

(3) Where run through doorways, windows, or similar openings

(4) Where attached to building surfaces

Exception to (4): Flexible cord and cable shall be permitted to be attached to building surfaces in accordance with the provisions of 368.56(B)

(5) Where concealed by walls, floors, or ceilings or located above suspended or dropped ceilings

(6) Where installed in raceways, except as otherwise permitted in this Code

(7) Where subject to physical damage

2017 Code Language:

400.12 Uses Not Permitted. Unless specifically permitted in 400.10, flexible cables, flexible cord sets, and power supply cords shall not be used for the following:

(1) As a substitute for the fixed wiring of a structure

(2) Where run through holes in walls, structural ceilings, suspended ceilings, dropped ceilings, or floors

(3) Where run through doorways, windows, or similar openings

(4) Where attached to building surfaces

Exception to (4): Flexible cord and flexible cable shall be permitted to be attached to building surfaces in accordance with 368.56(B).

(5) Where concealed by walls, floors, or ceilings or located above suspended or dropped ceilings

Exception to (5): Flexible cord and flexible cable shall be permitted if contained within an enclosure for use in Other Spaces Used for Environmental Air as permitted by 300.22(C)(3).

(6) Where installed in raceways, except as otherwise permitted in this Code

(7) Where subject to physical damage

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

400.12 Uses Not Permitted.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Which of the following flexible cords can be installed above a suspended ceiling?

A: An exposed flexible cord that is hard-wired, without a plug.
B: A flexible cord inside a metal enclosure.
C: An exposed flexible cord for a non-plenum rated condensate pump.
D: An exposed flexible cord for a ceiling-mounted projector.
Please register or sign in for electrical continuing education courses.

If you were already signed in, your session probably expired, please sign back in.