334.3 Securing and Supporting.

Cable ties marked Type 2S and 21S have been evaluated for the support of cables.
Click to Enlarge
Cable ties marked Type 2S and 21S have been evaluated for the support of cables.

Code Change Summary: Changes were made for cable ties used to support nonmetallic-sheathed cable.

The most common method used to secure and support nonmetallic-sheathed cables is staples but the NEC® also allows cable ties, straps, hangers, or similar fittings.

Not all cable ties are created equal. Some have only been evaluated to secure or position a cable. UL considers a cable tie a “cable positioning device” and certifies them to UL 62275.

The information listed below can be found using UL Product Spec under product category ZODZ: (Pay close attention to the last paragraph below).

RATINGS

Type Designations for Products Investigated to ANSI/UL 62275

Below is a preview of Article 334. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to the 2017 NEC® edition of NFPA 70.

2014 Code Language:

334.30 Securing and Supporting. Nonmetallic-sheathed cable shall be supported and secured by staples, cable ties, straps, hangers, or similar fittings designed and installed so as not to damage the cable, at intervals not exceeding 1.4 m (4 ½ ft) and within 300 mm (12 in.) of every outlet box, junction box, cabinet, or fitting.

2017 Code Language:

334.30 Securing and Supporting. Nonmetallic-sheathed cable shall be supported and secured by staples; cable ties listed and identified for securement and support; or straps, hangers, or similar fittings designed and installed so as not to damage the cable, at intervals not exceeding 1.4 m (4 ½ ft) and within 300 mm (12 in.) of every cable entry into enclosures such as outlet boxes, junction boxes, cabinets, or fittings.

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

334.3 Securing and Supporting.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Which of the following is required when supporting nonmetallic-sheathed cables?

A: Cable ties are NOT permitted.
B: Staples are NOT permitted.
C: Straps are NOT permitted.
D: If cable ties are used, they shall be listed and identified for securement and support.
Please register or sign in for electrical continuing education courses.

If you were already signed in, your session probably expired, please sign back in.