300.5(G) Raceway Seals.

These spare underground feeder raceways (circled in the left photo) enter the bottom of the switchgear in a way that moisture inside them cannot contact live parts. They must be sealed per 225.27 rather than 300.5(G). The rat on the other hand was living inside the switchgear and stealing pink insulation from a vacant suite through a spare raceway. For his last meal, he decided to lay down across the live busbars and then have a taste of the grounded metal enclosure.
Click to Enlarge
These spare underground feeder raceways (circled in the left photo) enter the bottom of the switchgear in a way that moisture inside them cannot contact live parts. They must be sealed per 225.27 rather than 300.5(G). The rat on the other hand was living inside the switchgear and stealing pink insulation from a vacant suite through a spare raceway. For his last meal, he decided to lay down across the live busbars and then have a taste of the grounded metal enclosure.

Code Change Summary: Spare raceways are now required to be sealed.

Section 300.5 is all about underground installations. Subsection 300.5(G) provides the rules on proper sealing of underground raceways in order to avoid condensation and moisture from entering an enclosure from the raceway and making contact with live parts.

Section 300.5(G) does not apply to every type of installation. It only applies when there is a chance that moisture inside the raceway may contact live parts.

Not all raceways are arranged in a manner that moisture inside them can contact live parts. Many underground raceways stub up into the floor of an open-bottom switchgear, far below the level of live parts. On the other hand, panelboards installed in a basement may be fed from a raceway that is underground while standing outside at grade level but then penetrates the wall of the basement above the panelboard. Proper raceway sealing must be done to ensure moisture inside the raceway doesn’t make its way into the panelboard and drip onto any live parts in the enclosure. See section 225.27 for additional sealing requirements pertaining to outside branch circuits and feeders.

In the 2014 NEC®, conduits or raceways through which moisture may contact live parts must be sealed or plugged at either or both ends. In the 2017 NEC®, this still remains true but now the rule also applies to spare or unused raceways.

Condensation and moisture from an underground raceway can just as easily enter an enclosure whether conductors are installed in the raceway or not. As well, spare raceways are a wonderful way for rodents and other living things to make their way into a place they shouldn’t be (see image).

Below is a preview of Article 300. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to the 2017 NEC® edition of NFPA 70.

2014 Code Language:

300.5(D)(G) Raceway Seals. Conduits or raceways through which moisture may contact live parts shall be sealed or plugged at either or both ends.

2017 Code Language:

300.5(D)(G) Raceway Seals. Conduits or raceways through which moisture may contact live parts shall be sealed or plugged at either or both ends. Spare or unused raceways shall also be sealed. Sealants shall be identified for use with the cable insulation, conductor insulation, bare conductor, shield, or other components.

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

300.5(G) Raceway Seals.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Which of the following is true for underground raceways?

A: Raceways containing conductors must be sealed at both ends.
B: Spare raceways shall be sealed or plugged at both ends.
C: Spare raceways through which moisture may contact live parts shall be sealed or plugged at either or both ends.
D: Spare raceways are NOT required to be sealed.
Please register or sign in for electrical continuing education courses.