250.80 Service Raceways and Enclosures.

A similar code change occurred in 250.86 for other than service raceways.
Click to Enlarge
A similar code change occurred in 250.86 for other than service raceways.

Code Change Summary: The exception allowing an isolated metal elbow to remain ungrounded if at least 18 inches deep has been revised.

The previous wording in the 2014 NEC® exception to 250.80 could be a bit misleading for those who like to play word games rather than install based on the intent of the code section.

The main rule for grounded electrical systems is to require all metal enclosures and raceways for service conductors and equipment to be connected to the grounded system conductor. The 2014 exception to the rule stated that a metal elbow, installed in an underground nonmetallic raceway, and isolated from possible contact by a minimum cover of 18 inches “to any part of the elbow” shall not be required to be connected to the grounded system conductor or grounding electrode conductor.

Technically, one could comply with the letter of the previous code language by installing the lowest part of a large pull elbow with at least 18 inches of cover while the upper portion of the pull elbow extends shallower or even above grade (see image).

The revised 2017 text makes it clear that the rule applies to all metal components (not just metal elbows) that are installed in a run of underground nonmetallic raceway. As well, the exception clears up the depth issue. Now, an isolated metal component can remain ungrounded if it has a minimum cover of 18 in. to all parts of the metal component.

A similar change occurred in 250.86 pertaining to isolated metal components used in underground runs of nonmetallic raceways, other than service raceways.

Below is a preview of Article 250. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to the 2017 NEC® edition of NFPA 70.

2014 Code Language:

250.80 Service Raceways and Enclosures. Metal enclosures and raceways for service conductors and equipment shall be connected to the grounded system conductor if the electrical system is grounded or to the grounding electrode conductor for electrical systems that are not grounded.

Exception: A metal elbow that is installed in an underground nonmetallic raceway and is isolated from possible contact by a minimum cover of 450 mm (18 in.) to any part of the elbow shall not be required to be connected to the grounded system conductor or grounding electrode conductor.

2017 Code Language:

250.80 Service Raceways and Enclosures. Metal enclosures and raceways for service conductors and equipment shall be connected to the grounded system conductor if the electrical system is grounded or to the grounding electrode conductor for electrical systems that are not grounded.

Exception: Metal components that are installed in a run of underground nonmetallic raceway(s) and are isolated from possible contact by a minimum cover of 450 mm (18 in.) to all parts of the metal components shall not be required to be connected to the grounded system conductor, supply side bonding jumper, or grounding electrode conductor.

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

250.80 Service Raceways and Enclosures.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Which of the following metal components in a run of underground nonmetallic service raceway can remain ungrounded?

A: An isolated metal pull elbow installed so that all parts of the elbow have at least 18 inches of cover.
B: An isolated metal pull elbow installed so that the elbow has 12 inches of cover.
C: A metal pull elbow installed so that the elbow emerges from grade.
D: A rigid metal pull elbow installed so that the elbow has 6 inches of cover.