210.3 Other Articles for Specific-Purpose Branch Circuits.

Code references listed in Table 210.3 can modify or amend the requirements in article 210 even if the illustration in 90.3 says otherwise.
Click to Enlarge
Code references listed in Table 210.3 can modify or amend the requirements in article 210 even if the illustration in 90.3 says otherwise.

Code Change Summary: Section 210.2 was renumbered to 210.3 and rewording makes it clear that something in chapter 4 can modify Article 210 requirements where referenced.

The general rule is, only Chapters 5, 6, and 7 can modify the rules in chapters 1-4 (see illustration in NEC® 90.3 and image on screen). There’s always an exception to the rule. Even though this code change is not really an exception, it still applies.

This is another one of those code sections that requires a careful read in order to grasp what the code change is trying to accomplish.

The revised code language simply states that Table 210.3 provides references for specific equipment and applications not located in Chapters 5, 6, or 7 that amend or supplement the requirements of this article.

When looking at Table 210.3, most code references in the Table come from Chapter 4 and even one from Chapter 3.

In simple terms, code references listed in Table 210.3 can modify or amend the requirements in article 210 even if the illustration in 90.3 says otherwise.

Below is a preview of Article 210. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to the 2017 NEC® edition of NFPA 70.

2014 Code Language:

210.2 Other Articles for Specific-Purpose Branch Circuits.

Branch circuits shall comply with this article and also with the applicable provisions of other articles of this Code. The provisions for branch circuits supplying equipment listed in Table 210.2 amend or supplement the provisions in this article.

2017 Code Language:

210.3 Other Articles for Specific-Purpose Branch Circuits.

Table 210.3 lists references for specific equipment and applications not located in Chapters 5, 6, and 7 that amend or supplement the requirements of this article.

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

210.3 Other Articles for Specific-Purpose Branch Circuits.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Which of the following is true when sizing a branch circuit for fixed electric space heating equipment?

A: Only Article 210 requirements are used to size the branch circuit.
B: Article 210 requirements are used except where 424.3 modifies the rules in 210.
C: Fixed electric space heating is a non-continuous load.
D: Blower motors used in fixed electric space heating are non-continuous loads.
Please register or sign in for electrical continuing education courses.