110.27(A) Live Parts Guarded Against Accidental Contact.

Open conductive rails on a traveling crane are considered “live parts”.
Click to Enlarge
Open conductive rails on a traveling crane are considered “live parts”.

Code Change Summary: Measurements have been added to address guarding of live parts up to 1000 volts.

There are many ways that exposed live parts can be guarded from accidental contact.

The NEC® defines “exposed” and “live parts” as follows:

Section 110.27 provides the following methods for the guarding of live parts:

  1. Guarding by using enclosures, rooms or vaults.
  2. Guarding by using partitions or screens.
  3. Guarding by locating equipment on balconies or elevated platforms.
  4. Guarding by specific dimensions above the floor or work surface based on voltage levels of the live parts.

In the 2017 NEC®, Item 4 above was modified to address live parts operating between 601 volts and 1000 volts. If item 4 above is used as a method to guard the live parts from accidental contact, then the live parts between 601 and 1000 volts must be at least 8 ft. 7 in. above floor.

Below is a preview of Article 110. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to the 2017 NEC® edition of NFPA 70.

2014 Code Language:

110.27(A)(4) Live Parts Guarded Against Accidental Contact.

By elevation above the floor or other working surface as shown in 110.27(A)(4)(a) or (b) below:

a. A minimum of 2.5 m (8 ft) for 50 to 300 volts

b. A minimum of 2.6 m (8 ½ ft) for 301 to 600 volts.

2017 Code Language:

110.27(A)(4) Live Parts Guarded Against Accidental Contact.

By elevation above the floor or other working surface as follows:

a. A minimum of 2.5 m (8 ft) for 50 volts to 300 volts between ungrounded conductors

b. A minimum of 2.6 m (8 ft 6 in.) for 301 volts to 600 volts between ungrounded conductors

c. A minimum of 2.62 m (8 ft 7 in.) for 601 volts to 1000 volts between ungrounded conductors.

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

110.27(A) Live Parts Guarded Against Accidental Contact.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

The conductive energized runway rail on a traveling crane, operating at 240 volts (measured between ungrounded conductors) is considered guarded if located at least how high above the floor?

A: 8 feet.
B: 8 ft. 6 in.
C: 6 feet.
D: 6.5 feet.
Please register or sign in for electrical continuing education courses.

If you were already signed in, your session probably expired, please sign back in.