110.26(A)(5) Separation from High-Voltage Equipment.

Switchgear in the far room operates at 12,470 volts while equipment in the closest room operates at 480 volts. The 3 hour barrier and fire rated door creates the suitable partition required by the new code section. Are there any other issues to be concerned about in the image?
Click to Enlarge
Switchgear in the far room operates at 12,470 volts while equipment in the closest room operates at 480 volts. The 3 hour barrier and fire rated door creates the suitable partition required by the new code section. Are there any other issues to be concerned about in the image?

Code Change Summary: A new code section requires separation when equipment operating at 1000 volts or less is located in the same vault, room or enclosure as equipment operating over 1000 volts.

Read carefully, this can be a big change, depending on how it is interpreted.

“Where switches, cutouts, or other equipment operating at 1000 volts, nominal, or less are installed in a vault, room, or enclosure where there are exposed live parts or exposed wiring operating over 1000 volts, nominal, the high-voltage equipment shall be effectively separated from the space occupied by the low voltage equipment by a suitable partition, fence, or screen”.

>

This code change is likely to see additional changes in 2020 because of the subjective terminology (in bold) that leaves much open for interpretation. Below is a breakdown of the loose code language that can create issues when applying this code change:

This code change, when applied as intended, can create a safer work situation. The code change will most likely affect indoor electrical rooms at large facilities where switchgear often operates at 12,470 volts or more.

Below is a preview of Article 110. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to the 2017 NEC® edition of NFPA 70.

2017 Code Language:

N 110.26(A)(5) Separation from High-Voltage Equipment.

Where switches, cutouts, or other equipment operating at 1000 volts, nominal, or less are installed in a vault, room, or enclosure where there are exposed live parts or exposed wiring operating over 1000 volts, nominal, the high-voltage equipment shall be effectively separated from the space occupied by the low voltage equipment by a suitable partition, fence, or screen.

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

110.26(A)(5) Separation from High-Voltage Equipment.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Which of the following equipment in the same room requires separation from one another?

A: 480-volt switchgear on one side and exposed PV system conductors operating at 1200 volts DC on the other.
B: 480-volt switchgear on one side and 208-volt panelboards on the other.
C: 208-volt switchgear on one side and a 112.5 KVA 208/480-volt step up transformer on the other.
D: 347-volt switchgear on one side and 480-volt panelboards on the other.
Please register or sign in for electrical continuing education courses.