210.12(B) Branch Circuit Extensions or Modifications - Dwelling Units.

AFCI protection shall not be required where the extension of the existing conductors is not more than 6 ft. and does not include any additional outlets or devices.
Click to Enlarge
AFCI protection shall not be required where the extension of the existing conductors is not more than 6 ft. and does not include any additional outlets or devices.

Code Change Summary: A new exception has been added to allow branch circuit extensions or modifications up to 6 ft.

AFCI protection requirements first appeared in the 1999 NEC® and the requirements have changed every code cycle since then.

When branch circuits are modified, replaced, or extended in areas of a dwelling that now require AFCI protection, AFCI protection must be installed to protect these modified branch circuits. This applies even in older homes that were built long before AFCI protection first appeared in the code book. This has been required since the 2011 NEC®.

In a dwelling unit, AFCI protection applies to 120-volt, single-phase, 15- or 20-ampere branch circuits supplying outlets or devices in kitchens, family rooms, dining rooms, living rooms, parlors, libraries, dens, bedrooms, sunrooms, recreation rooms, closets, hallways, laundry areas, or similar rooms or areas.

Now, a new exception allows a branch circuit extension up to 6 ft. to remain without the need to install AFCI protection, as long as no additional outlets or devices are installed. This gives a bit of relief for older homes where a fuse box is replaced with a newer panelboard installed adjacent to the old fuse box location. As long as branch circuits are not extended more than 6 ft. to make terminations on the new circuit breakers, AFCI protection is not required.

Below is a preview of the NEC®.  See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on the “free access” tab and select the applicable year of NFPA 70 (National Electrical code).

2011 Code Language:

210.12(B) Branch Circuit Extensions or Modifications — Dwelling Units. In any of the areas specified in 210.12(A), where branch-circuit wiring is modified, replaced, or extended, the branch circuit shall be protected by one of the following:

(1) A listed combination-type AFCI located at the origin of the branch circuit.

(2) A listed outlet branch-circuit type AFCI located at the first receptacle outlet of the existing branch circuit.

2014 Code Language:

210.12(B) Branch Circuit Extensions or Modifications — Dwelling Units. In any of the areas specified in 210.12(A), where branch-circuit wiring is modified, replaced, or extended, the branch circuit shall be protected by one of the following:

(1) A listed combination-type AFCI located at the origin of the branch circuit.

(2) A listed outlet branch-circuit type AFCI located at the first receptacle outlet of the existing branch circuit.

Exception: AFCI protection shall not be required where the extension of the existing conductors is not more than 1.8 m (6 ft) and does not include any additional outlets or devices.

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

210.12(B) Branch Circuit Extensions or Modifications - Dwelling Units.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Which of the following is true when extending an existing branch circuit in the bedroom of a home built in 1975?

A: It can remain without AFCI protection if the extension is 6 ft. or less and no additional devices or outlets are added.
B: If an additional receptacle is added, it can remain without AFCI protection as long as the extension is 6 ft. or less.
C: The new branch circuit extension must be done with a metallic wiring method.
D: The branch circuit extension must not be AFCI protected.
Please register or sign in for electrical continuing education courses.

If you were already signed in, your session probably expired, please sign back in.