680.7(C) Grounding and Bonding Terminals.

Some grounding and bonding fittings that are listed for use in wet and corrosive environments are marked “direct burial” or “DB” as in the image.
Click to Enlarge
Some grounding and bonding fittings that are listed for use in wet and corrosive environments are marked “direct burial” or “DB” as in the image.

Grounding and bonding terminals related to the pool installation are required to be identified for use in wet and corrosive environments.

Grounding and bonding terminals for pools, spas, or hot tubs are subjected to severe environmental conditions as well as corrosive chemicals such as chlorine and acid. Specifically requiring grounding terminals to be listed for wet and corrosive environments helps to address those conditions.

Section 680.7(C) states that “Terminals used for bonding and equipment grounding shall be identified for use in wet locations. Field-installed terminals in damp or wet locations or corrosive environments shall be composed of copper, copper alloy, or stainless steel and shall be listed for direct burial use”.

Throughout Article 680, a precedence has been established that typically allows brass to be used when something metal is required to be corrosion resistant. This code section does not mention brass but it does mention copper alloy. Here are a few facts that may provide additional insight:

Below is a preview of the NEC®. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to NFPA 70.

2023 Code Language:

680.7(C) Terminals. Terminals used for bonding and equipment grounding shall be identified for use in wet locations. Field-installed terminals in damp or wet locations or corrosive environments shall be composed of copper, copper alloy, or stainless steel and shall be listed for direct burial use.

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

680.7(C) Grounding and Bonding Terminals.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Which of the following bonding terminals is permitted for use with pool equipment?

A: A copper terminal that is listed for direct burial.
B: A zinc terminal.
C: An aluminum terminal.
D: A copper terminal that is listed for above ground use only.
Please register or sign in for electrical continuing education courses.