Article 722 Cables for Power-Limited Circuits and Fault-Managed Power Circuits.

CI cable, a fire-resistive cable system, or a listed electrical circuit protective system shall be permitted for use in systems that supply critical circuits to ensure survivability for continued circuit operation for a specified time under fire conditions.
Click to Enlarge
CI cable, a fire-resistive cable system, or a listed electrical circuit protective system shall be permitted for use in systems that supply critical circuits to ensure survivability for continued circuit operation for a specified time under fire conditions.

Code Change Summary: New Article 722 provides cable requirements for power-limited circuits and fault-managed power circuits.

In the 2023 NEC®, new Article 722 provides general requirements for the installation of single- and multiple-conductor cables used in Class 2 and Class 3 power-limited circuits, power-limited fire alarm (PLFA) circuits, and Class 4 fault-managed power circuits.

Language was pulled from other Chapter 7 articles to provide one location having requirements on power-limited circuits and Class 4 circuits.

Highlights in new Article 722 include:

Below is a preview of the NEC®. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to the 2023 NEC® edition of NFPA 70.

2020 Code Language:

This article did not exist.

2023 Code Language:

722.1 Scope. This article covers the general requirements for the installation of single- and multiple-conductor cables used in Class 2 and Class 3 power-limited circuits, power-limited fire alarm (PLFA) circuits, and Class 4 fault-managed power circuits.

722.179 Listing and Marking of Cables.

(A) Listing of Cables. Cables installed as wiring methods within buildings shall be listed as resistant to the spread of fire and other criteria in accordance with 722.179(A)(1) through (A)(16).

(16) Class 4 Cable Construction.

(1) Sizes. Conductors of sizes not smaller than 24 AWG shall be permitted to be used.

(2) Insulation. Insulation on conductors shall be rated not less than 450 volts dc.

(3) Voltage Rating. Cables shall have a voltage rating of not less than 450 volts dc. Voltage ratings shall not be marked on the cables.

(4) Temperature Rating. Cables shall have a temperature rating of not less than 60°C (140°F).

(5) Cabling. Cables shall comply with any requirements provided in the listing of the system.

Question 193

Based on the 2023 NEC, which of the following is true for Class 4 cable construction?

A: Conductor insulation shall be rated not less than 600 volts dc.
B: Insulation on conductors shall be rated not less than 450 volts dc.
C: Conductor insulation shall be rated not less than 1000 volts dc.
D: Conductor insulation shall be rated not less than 1500 volts dc.
Please register or sign in for electrical continuing education courses.

If you were already signed in, your session probably expired, please sign back in.