625.40 Electric Vehicle Branch Circuit.

An individual branch circuit is only required for EVSE outlets greater than 16 amperes or 120 volts.
Click to Enlarge
An individual branch circuit is only required for EVSE outlets greater than 16 amperes or 120 volts.

Code Change Summary: Revised language pertaining to branch circuits for electric vehicle charging.

Section 625.40 in the 2020 NEC® required all electric vehicle supply equipment (EVSE) to be supplied by an individual branch circuit that serves no other outlets regardless of the size (or level) of the vehicle charger.

There are three levels of EV charging:

In the 2023 NEC®, a public input was accepted to remove the code language previously requiring an individual branch circuit for ALL EVSE outlets. The revised 2023 language in Section 625.40 now requires an individual branch circuit only for EVSE outlets greater than 16 amperes or 120 volts. Additionally, a new exception to 625.40 now allows branch circuits to feed multiple EVSE’s as permitted by 625.42(A) or (B).

The previous rule requiring an individual branch circuit for all EVSE outlet applications was excessive for level 1 charging.

Below is a preview of the NEC®. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to the 2023 NEC® edition of NFPA 70.

2020 Code Language:

625.40 Electric Vehicle Branch Circuit. Each outlet installed for the purpose of charging electric vehicles shall be supplied by an individual branch circuit. Each circuit shall have no other outlets.

2023 Code Language:

625.40 Electric Vehicle Branch Circuit. Each outlet installed for the purpose of supplying EVSE greater than 16 amperes or 120 volts shall be supplied by an individual branch circuit.

Exception: Branch circuits shall be permitted to feed multiple EVSEs as permitted by 625.42(A) or (B).

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

625.40 Electric Vehicle Branch Circuit.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Based on the revised 2023 NEC language in 625.40, which of the following is true?

A: All EVSE outlets require an individual branch circuit.
B: All EVSE outlets require a multiwire branch circuit.
C: An individual branch circuit is only required for EVSE outlets greater than 16 amperes or 120 volts.
D: All EVSE outlets require a dedicated circuit.
Please register or sign in for electrical continuing education courses.