555.15 Replacement of Equipment.

Existing equipment that has been damaged must be identified, documented, and repaired by a qualified person.
Click to Enlarge
Existing equipment that has been damaged must be identified, documented, and repaired by a qualified person.

Code Change Summary: New Section 555.15 addresses the replacement of equipment.

In the 2023 NEC®, new Section 555.15 was added to provide requirements for modifications or replacements of electrical enclosures, devices, and wiring methods at docking facilities. The new code language can be broken down as follows:

During the 2023 NEC® first draft meetings, the wording in new Section 555.15 would have required any modification, replacement, or repair of electrical enclosures, devices, or wiring methods on a docking facility to be done so and inspected based on the current edition of the NEC®.

During the second draft meetings, the new code language was reworded to make it clear that only the “repairs” made to existing damaged equipment must meet the minimum requirements of the edition of the NEC® used when the equipment was originally installed.

Electrical systems installed on docking facilities and marinas are exposed to extremely harsh environmental conditions. Routine inspection and maintenance are needed to ensure a safe operation.

The new informational note in 555.15 refers the code reader to NFPA 303-2021, Fire Protection Standard for Marinas and Boatyards, which provides inspection guidance for electrical hazards at marinas and related facilities.

NFPA 303 Section 5.20.1 suggests inspecting all electrical wiring, grounding connections, conduits, hangers, supports, connections, outlets, appliances, devices, and portable cables installed or used in a marina, boatyard, boat basin, or similar establishment at regular intervals in order to constitute a complete inspection at least annually.

Below is a preview of the NEC®. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to the 2023 NEC® edition of NFPA 70.

2020 Code Language:

This code section did not exist.

2023 Code Language:

N 555.15 Replacement of Equipment. When modifications or replacements of electrical enclosures, devices, or wiring methods are necessary on a docking facility, they shall be required to comply with the requirements of this Code, and the installation shall require an inspection of the circuit. Existing equipment that has been damaged shall be identified, documented, and repaired by a qualified person to the minimum requirements of the edition of this Code to which it was originally installed.

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

555.15 Replacement of Equipment.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Based on the language in 555.15, which of the following is true?

A: When it is necessary to modify a wiring method a docking facility, the modification must comply with the requirements of the edition of the code used when the wiring method was originally installed.
B: When it is necessary to modify an electrical enclosure at a docking facility, the modification must comply with the requirements of the edition of the code used when the enclosure was originally installed.
C: When it is necessary to modify an electrical device at a docking facility, the modification must comply with the requirements of the edition of the code used when the device was originally installed.
D: Existing equipment that has been damaged must be identified, documented, and repaired by a qualified person.
Please register or sign in for electrical continuing education courses.

If you were already signed in, your session probably expired, please sign back in.