547.26 Physical Protection.

Even exposed nonmetallic cable installations are easy targets for hungry rodents in non-agricultural buildings adjacent to other buildings used to confine livestock and under the purview of Article 547.
Click to Enlarge
Even exposed nonmetallic cable installations are easy targets for hungry rodents in non-agricultural buildings adjacent to other buildings used to confine livestock and under the purview of Article 547.

Code Change Summary: New language and an informational note added to address nonmetallic cables concealed in buildings connected to agricultural buildings with livestock confinement capabilities.

In the 2023 NEC® code language was added to Section 547.26 to prohibit nonmetallic cables from being concealed within walls and above ceilings of buildings (i.e., offices, lunchrooms, ancillary areas, etc.) or portions thereof, which are contiguous with or physically adjoined to livestock confinement areas.

Additionally, a new informational note mentions that rodents and other pests are common around agricultural installations and often damage nonmetallic cables by chewing the cable jacket and conductor insulation concealed within walls and ceilings of livestock containment areas.

Keep in mind that Article 547 applies to agricultural buildings or parts of a building or adjacent areas of similar or like nature as specified in 547.1(A) or (B), but some buildings or portions of buildings might serve multiple purposes. This code change addresses nonmetallic cables concealed within walls and above ceilings of buildings like offices, lunchrooms, areas that are ancillary to the main occupancy, or portions thereof, which are “contiguous” (adjacent, neighboring, bordering, abutting, connected to, touching) with or physically adjoined to livestock confinement areas.

If a building near an agricultural location is not contiguous to a livestock confinement area, then this code language does not apply.

A concealed cable that has been chewed to the point of insulation failure creates a fire hazard.

Even exposed cables in other nearby structures that are cut off and not connected to agricultural buildings (as in the image) can be easy targets for rodents and when compromised, can create a major shock hazard.

Below is a preview of the NEC®. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to the 2023 NEC® edition of NFPA 70.

2020 Code Language:

547.5(E) Physical Protection. All electrical wiring and equipment subject to physical damage shall be protected.

2023 Code Language:

547.26 Physical Protection. All electrical wiring and equipment subject to physical damage shall be protected.

Nonmetallic cables shall not be permitted to be concealed within walls and above ceilings of buildings (i.e., offices, lunchrooms, ancillary areas, etc.) or portions thereof, which are contiguous with or physically adjoined to livestock confinement areas.

Informational Note: Rodents and other pests are common around such installations and will damage nonmetallic cable by chewing the cable jacket and conductor insulation concealed within walls and ceilings of livestock containment areas of agricultural buildings.

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

547.26 Physical Protection.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Based on the 2023 NEC, which of the following is true?

A: Nonmetallic cables are NOT permitted for any agricultural building.
B: Nonmetallic cables are NOT permitted for any building near an agricultural building.
C: Nonmetallic cables are NOT permitted to be concealed within walls and above ceilings of buildings (i.e., offices, lunchrooms, ancillary areas, etc.) or portions thereof, which are contiguous with or physically adjoined to livestock confinement areas.
D: Nonmetallic cables used in areas in the vicinity of an agricultural building must be contained in rigid metal conduit.
Please register or sign in for electrical continuing education courses.

If you were already signed in, your session probably expired, please sign back in.