210.8(B) GFCI Protection for Other Than Dwelling Units.

This receptacle requires GFCI protection even though it may not be within 6 feet of the sink.
Click to Enlarge
This receptacle requires GFCI protection even though it may not be within 6 feet of the sink.

Code Change Summary: Several changes and new requirements occurred for GFCI protection in other than dwellings.

In the 2020 NEC®, Section 210.8(B) had 12 locations specified (for other than dwelling units) where GFCI protection was required for certain receptacles. Exceptions were intermixed among the 12 locations as applicable.

In the 2023 NEC®, this section was expanded to have 15 locations where GFCI protection is required for receptacles, and all exceptions were relocated to the end of the 15 list items.

The GFCI requirements in Section 210.8(B) apply to specific receptacles installed in any of the 15 locations in other than dwelling units. Receptacle types include:

New locations in Section 210.8(B) that trigger the GFCI protection requirements for receptacles include:

Line item 7 (previously item 5 and applied only to receptacles within 6 feet of a sink) retains the language on “sinks” but was expanded to address cord-and-plug-connected fixed* or stationary* appliances located within 6 feet of a sink even if the receptacle that supplies the appliance is located further than 6 feet from the sink. The intent is to address the hazards that may exist with a faulty appliance supplied by a receptacle rather than the hazard existing from the location of the receptacle.

*Keep in mind that the following Article 100 definitions of “Fixed”, “Fixed-in-Place” and “Stationary” currently only apply where used in Articles 625 and 680 but the below definitions might shed some light on the intent of 210.8(B)(7) until future code cycles broaden the use of the definitions.

Fixed (as applied to equipment). Equipment that is fastened or otherwise secured at a specific location. (680)

Fixed-in-Place. Mounting means of equipment using fasteners that require a tool for removal. (625)

Stationary (as applied to equipment). Equipment that is not moved from one place to another in normal use. (680)

UL 197 is the Standard for Commercial Electric Cooking Appliances and has several definitions pertaining to appliances in Section 2 including:

A Fixed Appliance as defined and used in UL 197 is “An appliance that is intended to be fastened in place or located in a dedicated space and is permanently wired to the branch circuit”.

Below is a preview of the NEC®. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to the 2023 NEC® edition of NFPA 70.

2020 Code Language:

210.8(B) Other Than Dwelling Units. All 125-volt through 250-volt receptacles supplied by single-phase branch circuits rated 150 volts or less to ground, 50 amperes or less, and all receptacles supplied by three-phase branch circuits rated 150 volts or less to ground, 100 amperes or less, installed in the locations specified in 210.8(B)(1) through (B)(12) shall have ground-fault circuit-interrupter protection for personnel.

(1) Bathrooms

(2) Kitchens or areas with a sink and permanent provisions for either food preparation or cooking

(3) Rooftops

See exception

(4) Outdoors

See exceptions

(5) Sinks — where receptacles are installed within 6 feet from the top inside edge of the bowl of the sink

See exceptions

(6) Indoor damp and wet locations

(7) Locker rooms with associated showering facilities

(8) Garages, accessory buildings, service bays, and similar areas other than vehicle exhibition halls and showrooms

(9) Crawl spaces — at or below grade level

(10) Unfinished areas of basements

See exception

(11) Laundry areas

(12) Bathtubs and shower stalls — where receptacles are installed within 6 feet of the outside edge of the bathtub or shower stall

2023 Code Language:

210.8(B) Other Than Dwelling Units. All 125-volt through 250-volt receptacles supplied by single-phase branch circuits rated 150 volts or less to ground, 50 amperes or less, and all receptacles supplied by three-phase branch circuits rated 150 volts or less to ground, 100 amperes or less, installed in the following locations shall be provided with GFCI protection:

(1) Bathrooms

(2) Kitchens

(3) Areas with sinks and permanent provisions for food preparation, beverage preparation, or cooking

(4) Buffet serving areas with permanent provisions for food serving, beverage serving, or cooking

(5) No change from previous.

(6) No change from previous.

(7) Sinks where receptacles or cord-and-plug-connected fixed or stationary appliances are installed within 6 feet from the top inside edge of the bowl of the sink

(8) No change from previous.

(9) No change from previous.

(10) No change from previous.

(11) No change from previous.

(12) No change from previous.

(13) Aquariums, bait wells, and similar open aquatic vessels or containers, such as tanks or bowls, where receptacles are installed within 6 feet from the top inside edge or rim or from the conductive support framing of the vessel or container

(14) No change from previous.

(15) No change from previous.

See all exceptions

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

210.8(B) GFCI Protection for Other Than Dwelling Units.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Which of the following was added to Section 210.8(B) in the 2023 NEC?

A: Areas with permanent provisions for maintenance.
B: Areas with permanent provisions for servicing equipment.
C: Areas that might not be considered a “kitchen” but have a sink and permanent provisions for beverage preparation or cooking.
D: Areas with permanent provisions for remanufacturing.
Please register or sign in for electrical continuing education courses.

If you were already signed in, your session probably expired, please sign back in.