110.26(A)(4) Limited Access.

Code Violation! The space in front of the enclosure shall comply with the depth requirements of Table 110.26(A)(1) and shall be unobstructed to the floor by fixed cabinets, walls, or partitions.
Click to Enlarge
Code Violation! The space in front of the enclosure shall comply with the depth requirements of Table 110.26(A)(1) and shall be unobstructed to the floor by fixed cabinets, walls, or partitions.

Code Change Summary: Previous requirements for equipment installed in a space with limited access have been expanded.

In the 2014 NEC®, language was introduced in 424.66(B) to require working space above a suspended ceiling for duct heaters. In the 2017 NEC®, this language that was specific to only duct heaters was removed from 424.66(B) and relocated to Article 110 where it now applies generally to anything with limited access that may be examined or worked on while energized.

In the 2023 NEC®, this section was expanded to provide additional clarity for situations where fixed cabinets, walls, or partitions could create an obstacle for the electrician attempting to work on equipment above a suspended ceiling.

Now, the space in front of the enclosure must be unobstructed to the floor by fixed cabinets, walls, or partitions.

Before the code change in 2023, these requirements did not adequately address situations where the required working space for equipment above the ceiling might occur above fixed cabinets, walls, or partitions.

When this happens, it is almost impossible to work in front of the open enclosure from a ladder which creates a safety hazard.

In addition to the above change, the side reach distance in relation to horizontal ceiling “structural members” (such as a main runner of a grid ceiling) is now addressed.

A horizontal ceiling structural member or access panel is permitted to encroach into the required working space for the equipment if the location of weight-bearing structural members does not result in a side reach of more than 6 inches to work within the enclosure.

Below is a preview of the NEC®. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to the 2023 NEC® edition of NFPA 70.

2020 Code Language:

110.26(A)(4) Limited Access. Where equipment operating at 1000 volts, nominal, or less to ground and likely to require examination, adjustment, servicing, or maintenance while energized is required by installation instructions or function to be located in a space with limited access, all of the following shall apply: 

(4) The space in front of the enclosure shall comply with the depth requirements of Table 110.26(A)(1). The maximum height of the working space shall be the height necessary to install the equipment in the limited space. A horizontal ceiling structural member or access panel shall be permitted in this space.

2023 Code Language:

110.26(A)(4) Limited Access. Where equipment operating at 1000 volts, nominal, or less to ground and likely to require examination, adjustment, servicing, or maintenance while energized is required by installation instructions or function to be located in a space with limited access, all of the following shall apply:

(4) The space in front of the enclosure shall comply with the depth requirements of Table 110.26(A)(1) and shall be unobstructed to the floor by fixed cabinets, walls, or partitions. Space reductions in accordance with 110.26(A)(1)(b) shall be permitted. The maximum height of the working space shall be the height necessary to install the equipment in the limited space. A horizontal ceiling structural member or access panel shall be permitted in this space provided the location of weight-bearing structural members does not result in a side reach of more than 6 inches to work within the enclosure.

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

110.26(A)(4) Limited Access.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Based on the 2023 NEC, which of the following is true of electrical equipment installed above a suspended ceiling that is likely to be examined while energized?

A: A horizontal ceiling structural member or access panel shall be permitted in this space provided the location of weight-bearing structural members does not result in a side reach of more than 6 inches to work within the enclosure.
B: Partitions can encroach into the required work space.
C: Fixed cabinets can encroach into the required work space.
D: Walls can encroach into the required work space.
Please register or sign in for electrical continuing education courses.

If you were already signed in, your session probably expired, please sign back in.