110.22(A) Identification of Disconnecting Means.

In the 2023 NEC, not only is the circuit source required to be marked, but the “location” of the circuit source as well.
Click to Enlarge
In the 2023 NEC, not only is the circuit source required to be marked, but the “location” of the circuit source as well.

Code Change Summary: New language was added that requires marking the location of the circuit source.

Since 1965, the NEC® has required each disconnecting means to be legibly marked to indicate its purpose unless located and arranged so the purpose is evident.

If the purpose of a disconnecting means located remotely from the equipment it serves is not clear it requires field identification to identify what it supplies. On the other hand, the purpose of a disconnecting means located directly adjacent and connected to an air conditioner it serves is evident and further identification is not required.

In the 2020 NEC®, the existing language was expanded with another provision, specific to other than one- or two-family dwellings, requiring a disconnecting means to be field marked to identify the circuit source that supplies it.

In the 2023 NEC®, this concept was taken a step further. Now, if the purpose of a disconnecting means in other than one- or two-family dwellings is not evident, not only is the circuit source required to be marked, but the “location” of the circuit source as well.

It’s not enough to know that a circuit from panelboard H-1 supplies a remote disconnect if nobody knows where to find panel H-1.

This code change is a move to promote safety by ensuring that a service electrician or building owner can easily shut off the circuit supplying a disconnecting means in the event of a problem.

Below is a preview of the NEC®. See the actual NEC® text at NFPA.ORG for the complete code section. Once there, click on their link to free access to the 2023 NEC® edition of NFPA 70.

2020 Code Language:

110.22 Identification of Disconnecting Means.

(A) General. Each disconnecting means shall be legibly marked to indicate its purpose unless located and arranged so the purpose is evident. In other than one- or two-family dwellings, the marking shall include the identification of the circuit source that supplies the disconnecting means. The marking shall be of sufficient durability to withstand the environment involved.

2023 Code Language:

110.22 Identification of Disconnecting Means.

(A) General. Each disconnecting means shall be legibly marked to indicate its purpose unless located and arranged so the purpose is evident. In other than one- or two-family dwellings, the marking shall include the identification and location of the circuit source that supplies the disconnecting means unless located and arranged so the identification and location of the circuit source is evident. The marking shall be of sufficient durability to withstand the environment involved.

Did You Like This?   Follow us on Facebook!

Help Us Keep Our Knowledge Free!

Electrical License Renewal Facebook Logo

110.22(A) Identification of Disconnecting Means.

Below is a Real Question from our Electrical Continuing Education Courses for Electrical License Renewal:

Based on the 2023 NEC, which of the following is true if the purpose of a disconnect at an industrial building is NOT evident?

A: No marking is required.
B: It shall be marked “Disconnect”.
C: It shall be marked to include the identification and location of the circuit source that supplies the disconnecting means.
D: It shall be marked “Disconnect switch”.